EasyManuals Logo

KSB AmaControl INT 600 DM User Manual

KSB AmaControl INT 600 DM
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
1 Supplementary Operating Manual
28 of 48
AmaControl
2301.83/04-EN
Start End Description Data type
8527 8527 Sum over lifetime:
motor detected as running even though the relay was switched off
Message
The following error numbers are counted: {11},{118},{246}
u 16bit
8554 8554 Sum over lifetime:
power reset
Message
The following event numbers are counted: {1}
u 16bit
8555 8555 Sum over lifetime:
synchronisation of real-time clock
Message
The following event numbers are counted: {252}
u 16bit
8556 8556 Sum over lifetime:
reset via Modbus
Message
The following event numbers are counted: {253}
u 16bit
8557 8557 Sum over lifetime:
reset via switching input
Message
The following event numbers are counted: {254}
u 16bit
8558 8558 Sum over lifetime:
successful parameter change
Message
The following event numbers are counted: {249}
u 16bit
8612 8612 Current running time of the motor
0..65,535minutes
u 16bit
8614 8614 Number of running times <5minutes
Number to determine the quasi-percentage distribution
u 16bit
8615 8615 Number of running times 5 - 9minutes
Number to determine the quasi-percentage distribution
u 16bit
8616 8616 Number of running times 10 - 19minutes
Number to determine the quasi-percentage distribution
u 16bit
8617 8617 Number of running times 20 - 29minutes
Number to determine the quasi-percentage distribution
u 16bit
8620 8620 Number of running times 120 - 300minutes
Number to determine the quasi-percentage distribution
u 16bit
8621 8621 Number of running times > 300minutes
Number to determine the quasi-percentage distribution
u 16bit
8632 8632 Total number of starts of the current day (internal time) 0...255 u 16bit
8634 8634 Total number of starts of the previous day (current day - 1 day; internal
time)
0...255
u 16bit
8635 8635 Total number of starts two days ago (current day - 2 days; internal time)
0...255
u 16bit
8636 8636 Total number of starts three days ago (current day - 3 days; internal time)
0...255
u 16bit
8637 8637 Total number of starts four days ago (current day - 4 days; internal time)
0...255
u 16bit
8638 8638 Total number of starts five days ago (current day - 5 days; internal time)
0...255
u 16bit
8639 8639 Total number of starts six days ago (current day - 6 days; internal time)
0...255
u 16bit
8640 8640 Switching cycles of the current hour (internal time)
0...255
u 16bit
8641 8641 Maximum of the switching cycles per hour of the current day (internal
time) 0...255
u 16bit

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KSB AmaControl INT 600 DM and is the answer not in the manual?

KSB AmaControl INT 600 DM Specifications

General IconGeneral
BrandKSB
ModelAmaControl INT 600 DM
CategoryGateway
LanguageEnglish