EasyManua.ls Logo

Lamtec GUI607

Lamtec GUI607
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
236
8 CO/O
2
Control
4 Tab ’Behaviour during optimisation’
5 Maximum firing rate difference for static optimisation
During static optimisation, the internal firing rate is frozen. As soon as the requested fir-
ing rate exceeds the set value, the optimisation is stopped and the firing rate adjustment
is enabled again. Value range 0 ... 999 digit.
6 Time [s] to cancel a completed optimisation while the burner is running
Validity of the optimisation points adjustment.
Time value to start a new optimisation after a successful completion in hours.
Value range = 0 ... 17780 s.
Each optimisation point is treated individually. The time begins to run as soon as the
optimisation in the affected firing rate segment has been completed.
Factory setting: 28800 8 h.
7 Burner down time [Min]: After expiry the CO optimisation is released immediately after
the start of the controller
Factory setting: 60 Min*
* i. e. If the burner remains switched OFF for longer than 60 Min, the CO control is ena-
bled immediately after burner ON in order to counteract an earlier formation of CO in a
cold combustion chamber.

Table of Contents

Related product manuals