68
4 CMS Components
Allocation between Function and Bits see Parameter list DLT7202.
4.6.7 Interfaces
Failsafe communication via iLSB.
Type of
Input
Configuration Software Configuration Software
Sensors Connection Parameter IO-Matrix
Non-fail-
safe
1 per input = 1 nsi
signal
see Fig. 4-29 SAI connection dia-
gram
P 1270
Bit 0 ... 6: Function
Bit 7 = 0
Mapping as nsi AI
Failsafe,
linked
1 per 2 inputs =
1 si signal
see 4.6.6 Connection Diagram
Switch in parallel pairs IN+ and IN-
(Pin 2 and 3)
– Input 1 to 2
– Input 3 to 4
– Input 5 to 6
– Pt100/Pt1000:
Ref+ (PIN1) additional in parallel
P 1270
Bit 0 ... 6: Function
Bit 7 = 1
Mapping as si AI
Failsafe,
not linked
2 per 2 input = 1 si
signal
see Fig. 4-29 SAI connection dia-
gram
Sensor connections are independ-
ent to each other
P 1270
Bit 0 ... 6: Function
Bit 7 = 0
Mapping as si AI

Table of Contents