Starting up
28
The display shows the current bath temperature Xp
and the current setting. To alter the setting press the
key on the left. Available settings from 0,5 to 9,9 °C .
( Section 6.4.3.2.
Note).
( Section 9. Technical data)
Display flashes (approx. ca. 4 s).
or
During this time start to set the required value with one
of the two keys.
Forward with the key to "Setting the reset time" or
with the key back to "PARA".
6.4.3.2 Setting the reset time of the PID-controller
and 2x
Directly from level 0 (setpoint selection), press the key
combination on the left (top one on E 3xx, bottom one
E 2xx), until the PARA function is reached, then
and 1x
switch to level 2 and move forward with the keys on the
left.
The display shows the current bath temperature, Tn and
the current setting. To alter the setting, press the key on
the left.
!
Possible adjustment from 5 to 60 s
The display is flashing (approx. 4 s).