Appendix A Parameters List
1. Modbus RTU Parameters
The Leadshine RS485 parameter data type is 32-bit data, and a parameter contains two registers, high 16 bits and low 16 bits,
but in practice most parameters only need to use the low 16 bits. When reading and writing multiple parameters in succession,
the high 16 bits of the parameter need to be used as the start.
Forced enable by software
Software forced enable has a higher priority than
IO enable, and when this value is 0, the enable
status of the drive only depends on the IO signal.
When this value is 1, the motor is enabled
regardless of the IO signal status.
To configure the time for internal command
filtering
Default is normal-open(N.O) type, it can be set to
normal-closed(N.C) type by setting the
corresponding port +0x80
SI1 is enable(default), N.C type input.
0: invalid; 7: alarm clearing;
8: enable (also can be set by 0x00F);
0x20: Trigger command;
0x21: Trigger homing;
0x22: EMG (quick stop);
0x23: JOG+;
0x24: JOG-;
0x25: POT (positive limit);
0x26: NOT (negative limit);
0x27: ORG (home switch);
0x28: ADD0 (path address 0);
0x29: ADD1 (path address 1);
0x2A: ADD2 (path address 2);
0x2B: ADD3 (path address 3);
0x2C: JOG velocity 2
Default is normal-open(N.O) type, it can be set to
normal-closed(N.C) type by setting the
corresponding port +0x80
0: invalid;
0x20: command completed;
0x21: path completed;
0x22: homing completed;
0x23: in-position completed;
0x24: brake output;
0x25: alarm output;
Threshold value of brake
locking velocity
Alarm detection selection
Bit setting:
=1: Yes; =0: No
bit0: over-current ( Cannot be changed)
bit1: over-voltage
bit3: ADC sampling failure
bit4: Locked shaft alarm
bit5: EEPROM alarm
bit6: Auto-tuning alarm
Approximately equal to motor phase current value
multiplied by 1.4
522: 0-22
556: 0-56
870: 0-70
882: 0-82