Code Possible Settings
IMPORTANT
No. Name Default Selection
P108
Motor Overload 100 30 {%} 100
P109
Motor Overload
Type
0 0 Speed Compensation
Ir
100%
60%
30 f
1
0
V0108
1 No Speed Compensation
P110
Start Method 0 0 Normal
1 Start on Power-up Drive will automatically start when
power is applied.
2 Start with DC Brake When start command is applied, drive
will apply DC braking according to
P174, P175 prior to starting the motor
3 Auto Restart Drive will automatically restart after
faults, or when power is applied.
4 Auto Restart with DC Brake Combines settings 2 and 3
5 Flying Start/Restart #1 • Drive will automatically restart after
faults, or when power is applied.
• After 3 failed attempts, drive will
Auto Restart with DC brake.
• P110 = 5: Performs speed search,
starting at Max Frequency (P103)
• P110 = 6: Performs speed search,
starting at the last output frequency
prior to faulting or power loss
• If P111 = 0, a ying START is
performed when a start command
is applied.
6 Flying Start/Restart #2
motor current rating
P108 =
SM2 output rating
x 100
Example: motor = 3 amps; SM2 = 4
amps; P108 = 75%
Note
Do not set above the rated motor current as listed on the motor
dataplate. The motor thermal overload function of the SM2 is UL
approved as a motor protection device. If line power is cycled, the
motor thermal state is reset to cold state. Cycling power after an
overload fault could result in signicantly reducing the motor life.