SCS BUS AUTOMATION SYSTEM
GENERAL FEATURES
III-120
Actuators
These devices perform the controls received, and monitor the connected load in a similar way to an electro-mechanical relay.
For this reason, they must be connected to the SCS BUS cable using the removable terminals as well as to the 230 Vac supply
line of the load.
OVERVIEW OF THE ACTUATORS
This table lists the actuators divided by type of use.
Actuators BUS
absorption
Driven loads Dissipated
power
+
M
Incandescent
/halogen
lamps
+
M
Resistive
loads
Fluorescent
lamps
Electronic
transformers
+
M
Ferromagnetic
transformers
M
Rolling
shutter
motors
038 41
22 mA 10 A
2300 W
16 A
3500 W
4 A
1000 W
4 A
1000 W
4 A cos ϕ 0.5
1000 VA
- 1.5 W
038 42
28 mA
(Single loads)
15.5 mA
(Interlock)
6 A
1400 W
10 A
2300 W
1 A
250 W
1 A
250 W
2 A cos ϕ 0.5
500 VA
2 A
500 W
1.7 W
038 44
40 mA
(Single loads)
22 mA
(Interlock)
2 A
500 W
6 A
1400 W
0.3 A
70 W
0.3 A
70 W
2 A cos ϕ 0.5
500 VA
2 A
500 W
3.2 W
036 56
30 mA -
-
-
-
2 A
460 W
MAX 10 ballast
tipo T5, T8,
compatte o
driver per led.
-
-
-
-
-
-
0.5 W
036 52
9 mA 0.25 – 4 A
60 – 1000 W
0.25 – 4 A
60 – 1000 W
-
-
-
-
0.25 – 4 A
60 – 1000 VA
-
11 W
(Max. Load 1000 W)
5 W
(Max. Load 500 W)
036 53
9 mA -
-
-
-
-
-
0.25 – 1.7 A
60 – 400 VA
-
-
-
-
11 W
2 43 5
1
1 3
2 4
3
2
1