EasyManua.ls Logo

LEGRAND DMX3 Series - User Manual

LEGRAND DMX3 Series
140 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
DMX
3
Octobre 16
Y2958H

Questions and Answers

  • M
    Mallory MeyersAug 13, 2025
    What to do if LEGRAND Circuit breakers racking shutter does not re-close automatically?
    • V
      Valerie RogersAug 13, 2025
      If the LEGRAND Circuit breakers racking shutter doesn't re-close automatically after the racking handle is pulled out, it might be because the breaker is in-between the Service/Test/Isolated position. Ensure the position indicator is aligned with one of the distinct positions by racking the breaker in or out.
  • V
    Vicki WalkerAug 17, 2025
    What to do if LEGRAND Circuit breakers ACB trips after closing?
    • T
      Tonya MitchellAug 17, 2025
      If your LEGRAND Circuit breaker trips after closing, it could be due to a couple of reasons. If it trips after a few seconds or minutes, there may be an overload fault. Inspect the unit protection to identify the fault and then resolve the cause. Alternatively, the Shunt Release may be continuously receiving a command. In this case, verify the source of the command.
  • A
    Alicia WilkinsAug 21, 2025
    Why LEGRAND DMX3 ACB does not close on pressing “ON” button?
    • A
      Allen BallAug 21, 2025
      If your LEGRAND Circuit breakers ACB does not close when you press the “ON” button, it could be due to several reasons. First, the U/V release might be present but not energized; in this case, you should energize the U/V release. Second, the mechanism spring might not be charged; charge it manually until the spring status indicator turns yellow. Third, the reset button might be ejected; press the reset button. Finally, the mechanical interlock might be disabling closing; recheck before trying to close the breaker.
  • T
    Tabitha SmithAug 25, 2025
    Why LEGRAND DMX3 Circuit breakers ACB does not close electrically?
    • G
      Gregory PowellAug 25, 2025
      If the LEGRAND Circuit breakers ACB does not close electrically, it means that the “Ready to close” (RTC) conditions are not being met. You should check all RTC conditions to resolve this issue.
  • P
    Patrick TurnerAug 28, 2025
    How to fix LEGRAND Circuit breakers that can not be driven in Test and Service position?
    • E
      erin91Aug 28, 2025
      If the breaker cannot be driven into the Test and Service position, it is possible that the breaker and miss insertion device ratings do not match. Ensure that you put the correct breaker in place.
  • D
    David CharlesSep 1, 2025
    How to fix LEGRAND DMX3 ACB that does not close on pressing “ON” button?
    • C
      Carolyn JonesSep 2, 2025
      If the LEGRAND Circuit breakers ACB doesn't close when you press the “ON” button, consider these potential causes: * The selector for dielectric test might be in the “dielectric test position”—set it to the “normal use” position. * The U/V release may be present but not energized—energize the U/V release. * The mechanism spring might not be charged—manually charge it until you hear a distinct sound and the indicator turns yellow. * The reset button could be ejected—press the reset button. * The racking shutter might be open—close the racking shutter. * A mechanical interlock might be disabling closing—re-check before attempting to close the breaker.
  • N
    Natalie WrightSep 4, 2025
    What to do if LEGRAND DMX3 ACB does not close electrically?
    • S
      Stephanie BowersSep 5, 2025
      If the LEGRAND Circuit breakers ACB does not close electrically, it might be because the electrical antipumping is active. To resolve this, interrupt the ‘OPEN’ command once. Another reason could be that the “Ready to close”(RTC) conditions are not met, so you should check all RTC conditions.
  • K
    Kyle CarlsonSep 8, 2025
    Why LEGRAND DMX3 Circuit breakers ACB cannot be pushed in to isolated position?
    • N
      Nathaniel HooperSep 8, 2025
      The LEGRAND Circuit breakers ACB might not push into the isolated position if the breaker and miss insertion device ratings do not match. Ensure you are using the correct breaker.

Summary

Weights

Handling and unpacking

Storage for fixed and draw-out breakers

Identification

Racking-out frontal cover

Exploring

Operating

Technical specifications

General features

Overview of main electrical and mechanical characteristics.

Real dimensions of the device

Physical dimensions for installation and integration.

Net Weight

Weight information for handling and installation planning.

Features of the main electrical accessories

Motor operator

Technical features of the motor operator accessory.

Closing coil

Technical specifications for the closing coil accessory.

Shunt trip

Technical specifications for the shunt trip accessory.

Undervoltage release

Technical specifications for the undervoltage release accessory.

Time delayer for undervoltage release

Technical features of the time delay module for UVR.

Signal contact for auxiliaries

Technical features of auxiliary signal contacts.

Additional signalling contact

Technical features of additional signaling contacts.

Contact ready to close with charged springs

Technical features of the contact ready to close function.

Inserted;test;draw-out contacts

Technical features of inserted/test/draw-out contacts.

Module programmable output

Technical features of the programmable output module.

External auxiliary supply

Technical features of the external auxiliary supply.

Installation and door cut-out

Installation of breaker DMX3 fixed version

Mounting details for fixed version breakers.

Door cut-out for fixed version

Required door cut-out dimensions for fixed version.

Installation of breaker DMX3 draw-out version

Mounting details for draw-out version breakers.

Door cut-out and door drilling for draw-out version

Door cut-out and drilling for draw-out version.

Fixing Door Sealing Frame

Procedure for fixing the door sealing frame.

Termination - Fixed Breakers

DMX3 2500. 3 poles.

Termination details for 3-pole DMX3 2500 fixed breakers.

DMX3 4000. 3 poles.

Termination details for 3-pole DMX3 4000 fixed breakers.

DMX3 6300. 3 poles.

Termination details for 3-pole DMX3 6300 fixed breakers.

DMX3 2500. 4 poles.

Termination details for 4-pole DMX3 2500 fixed breakers.

DMX3 4000. 4 poles.

Termination details for 4-pole DMX3 4000 fixed breakers.

DMX3 6300. 4 poles.

Termination details for 4-pole DMX3 6300 fixed breakers.

Termination - Draw-out breakers

DMX3 2500. 3 poles flat terminals.

Termination details for 3-pole DMX3 2500 draw-out.

DMX3 4000. 3 poles flat terminals.

Termination details for 3-pole DMX3 4000 draw-out.

DMX3 6300. 3 poles flat terminals.

Termination details for 3-pole DMX3 6300 draw-out.

DMX3 2500. 4 poles flat terminals.

Termination details for 4-pole DMX3 2500 draw-out.

DMX3 4000. 4 poles flat terminals.

Termination details for 4-pole DMX3 4000 draw-out.

DMX3 6300. 4 poles flat terminals.

Termination details for 4-pole DMX3 6300 draw-out.

Connection for fixed version

DMX3 2500.

Connection details for DMX3 2500 fixed version.

DMX3 4000.

Connection details for DMX3 4000 fixed version.

DMX3 6300.

Connection details for DMX3 6300 fixed version.

Possible connections for draw-out version

Ground connection

Insertion on switchboard

Auxiliary terminals block

Shunt trip (ST)

Details on the Shunt Trip (ST) auxiliary function.

New cabling system

Electrical diagram

3 Poles

Electrical diagram for 3-pole configurations.

4 Poles

Electrical diagram for 4-pole configurations.

Dielectric test (if present)

Setting protection unit

Insertion;substitution battery

Procedure for inserting or substituting the battery.

Setting levels protection

How to set protection levels using rotary switches.

Setting data;time

Importance of setting date/time for fault archiving.

Seal of protection unit

Procedure to close and seal the protection unit cover.

Standard functions of the breaker

Reset button

Explanation of MAN and AUT positions for the reset button.

Trip contact

Technical features of the trip contact.

Padlock for racking shutter

Procedure for using a padlock on the racking shutter.

DMX3 start up

Operator checks

Initial checks by the operator for proper installation.

Without voltage checks

Inspection procedures without applying voltage.

Check of installed components correspondence to the electric diagram

Verifying component specifications match the electrical diagram.

Auxialiries wiring and installation check

Checks for auxiliary circuits and terminal wiring.

Under voltage checks

Procedures for dielectric checks and under-voltage tests.

Functioning check

Verifying mechanical functioning and contact operation.

Manual control

Performing manual opening/closing cycles.

Reasons fault

Common causes of faults and recommended checks.

In case of short circuit, device inspection

Inspection procedures following a short circuit event.

Device closing

Conditions and procedures for closing the device.

Identification of the fault

How faults are indicated and suggested actions.

Ordinary maintenance

Basic trouble shooting

LEGRAND DMX3 Series Specifications

General IconGeneral
BrandLEGRAND
ModelDMX3 Series
CategoryCircuit breakers
LanguageEnglish

Related product manuals