Page 3
SPECIFICATIONS CHA161353 & CHA161603
Model No. CHA161353 CHA161603
*
Total cooling capacity (btuh) 119,000 142,000
*ARI Standard
210/240 Ratin
s
Total unit watts 13,220 16,820
or
EER (Btuh/Watts) 9.0 8.50
an
ar
a
ngs
Integrated Part Load Value 8.8
ARI Standard 270 SRN (Bels) 8.8
Stage 1
10 lbs. 12 oz.
Refrigerant (22) Charge
Stage 2
7 lbs. 4 oz.
7 lbs. 12 oz.
Blower wheel nominal diameter x width (in.) 15 x 15
Nominal motor horsepower 2 3
**Factory
Maximum usable horsepower 2.30 3.45
Installed
Drives
Voltage & phase 208/230/460v3ph
vapora
or
ower
and
RPM range 730 950
Drive Selection
Nominal motor horsepower 3
**Optional
Factor
Maximum usable horsepower 3.45
Installed
Voltage & phase 208/230/460v3ph
Drives
RPM range 730 950
Net face area (sq. ft.) 9.46 11.9
Evaporator
Tube diameter (in.) & No. of rows 3/8 4 3/8 3
Fins per inch 12 12
Net face area (sq. ft.) 20.0 24.4
Condenser
Tube diameter (in.) & No. of rows 3/8 2 3/8 2
Fins per inch 20
Diameter (in.) & No. of blades (2) 20 5 (2) 22 4
Condenser
Air volume (cfm) 6400 Total 7700 Total
Fans
Motor horsepower (2) 1/3 (2) 1/2
Motor watts 875 Total 1050 Total
Condensate drain size mpt (in.) 3/4
No. & size of filters (in.) (4) 16 x 25 x 2 (4) 20 x 25 x 2
Electrical characteristics 208/230v or 460v 60 hertz 3 phase
Sound Rating Number in accordance with ARI Standard 270.
*Rated in accordance with ARI Standard 210/240 or
360; 95F outdoor air temperature and 80F db/67F wb entering evaporator air.
**Using total air volume and system static pressure requirements determine from blower performance tables rpm and bhp required. Maximum usable hp of motors
furnished by Lennox are shown. If motors of comparable hp are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
OPTIONAL ACCESSORIES CHA161353 & CHA161603 (Ordered Extra)
Unit Model No. CHA161353 CHA161603
Model No. ECH16135/160 ECH16135/160
Electric
Kw input range 1520304050
Heat
*Fuse
208/230 volt 72G10 72G13
Block
460 volt 72G11 72G14
Roof Mounting Frame RMF16135/160 (32G91)
Economizer Dampers No. & size of filters (in.) REMD16M135 (2) 16 x 25 x 1 (74G23) REMD16M160 (2) 20 x 25 x 1 (51G25)
Horizontal Economizer Dampers No. & size of filters (in.) EMDH16M135 (2) 16 x 25 x 1 (24H04) EMDH16M160 (2) 20 x 25 x 1 (24H05)
Exhaust Dampers (Net Face Area) GED1695/135/160 (0.43 sq. ft.) (34G80)
Differential Enthalpy Control 54G44
Horizontal Supply and Return Air Kit LB55756BB (35G42) LB55756BC (51G27)
Bottom Power Entry Kit (LB55757CA) 34G70
StepDown RTD11135 (29G05) RTD11185 (29G06)
e
ng
upp
y an
Return Air
Flush FD11135 (29G09) FD11185 (29G10)
Diffusers
Transition SRT16135 (97H10) SRT16160 (97H11)
Outdoor Air Dampers No. & size of filters (in.) OAD16135 (35G25) (1) 16 x 20 x 1 OAD16160 (51G30) (1) 16 x 20 x 1
Automatic OAD16 Damper Kit 35G21
Low Ambient Control Kit LB57113BH (16J86) LB57113BJ (16J87)
TimedOff Control (2) LB50709BA 40G20
*Must be ordered extra. Factory installed heaters will have fuse block installed. Fuse block must be field installed in field installed heaters.