CLIMATIC™50 – IOM – Rooftops/ Aircoolair CL50-ROOFTOPS-IOM-1107-E
9
[NTC] Temperature probe `NTC' on the sticks of the coils
[0-5V] Transmitter of pressure `Ratiométrique' on the circuits
[4-20mA] Transmitter of pressure `4-20mA ' on the circuits
3822 ! Activation of the Low Ambient Kit option,
3823 ! Unit with water condensation
3824 ! Activation of the Alternate Defrost option for the Flexy1 range sizes 85 and 100
3831 ! Choice of the auxiliary heating type.
[No] No auxillary heating
[Hot W/Coil] Hot water coil
[Gas 2] Gas, 1 slope with 2 steps
[Gas 4] Gas, 2 slopes with 2 steps
[Gas 2 Pro.] Gas, 1 modulating slope
[Gas 4 Pro.] Gas, 2 modulating slope
[ElecH. Ste] Electric heaters, without Triac modulation.
[ElecH. Pro] Electric heaters, with Triac, Positioned after the refrigerant coil
[ElecH. Mix] Electric heaters, with Triac, Positioned before the refrigerant coil
3711 ! Choice of the type of gas valves control board.
[BG50] Board BG50
[EF49] Board EF49
[EF48] Board EF48
[EF45] Board EF45
[MMI No] Block gas with output fault in normally open
[MMI Nc] Block gas with output fault in normally closed
3832 ! Choice of the type air mixing box
[No] No fresh air
[100%] All fresh air
[0%-100%] Economiser proportional
[0%-50%] Economiser proportional, limitation to 50% of opening
3517 ! Activation of the air heat recovery option,
3833 ! Choice of the type of air flow sensor
[No] No option
[500pa] Sensor, 0 to 500 pa
[1000pa] Sensor, 0 to 1000 pa
3834 ! Choice of the air quality sensor
[No] No option
[0-2000] Sensor, 0 to 2000 ppm
[350-2000] Sensor, 350 to 2000 ppm (Carel© brand sensor)