Overheating of Electrical Heating Elements
Error code: 011
Description
A safety thermostat in the electric heater unit has operated or the control contactor has not been activated.
Action
" Heating elements switched off immediately.
" Fault signalling. Memorisation is displayed.
Reset
Manual reset.
Possible causes Solving the problem
Air system obstructed or closed Check the system
Filters clogged Clean the filters
Broken belts Replace the belts
Problem with the wiring of the heating elements Check the connections