CLIMATIC™50 – IOM – Rooftops/ Aircoolair CL50-ROOFTOPS-IOM-1107-E
38
Condenser fans
Error code: 092, 093, 094, 095
Description
The condenser fan motor control is no longer active.
Action
" The compressors and fans in the circuit shut down immediately.
" Fault signalling.
If a DS50 is connected to the unit; Memorisation and diplay of all faults.
Otherwise; Memorisation and display only of the 3rd daily fault.
" Display of fault.
092, Fan; Circuit 1.
093, Fan; Circuit 2.
094, Fan; Circuit 3.
095, Fan; Circuit 4.
Reset
The safety device is automatically cancelled 30 minutes after activation.
The fault will no longer be reset automatically after 3 cutouts in the same day and must be reset manually.
Note: The fault counter is cleared and reset every day at 11 am, provided the maximum number of faults has not
been reached.
Possible causes Solving the problem
Motor thermal protection devices activated Check the air system
Motor thermal protection devices activated Check the motors
Problem with the fan wiring Check the connections