CLIMATIC™50 – IOM – Rooftops/ Aircoolair CL50-ROOFTOPS-IOM-1107-E
39
Water Condenser Faults
Error code: 096, 097, 098
Description
The water outlet temperature from the heat exchanger measured by the sensor is outside the permitted range or the
water flow detection device is not active.
Lower temperature limit: Water outlet temperature < safety threshold
Upper temperature limit: Water outlet temperature > safety threshold
2572 ! Temperature of circuit 1
2573 ! Temperature of circuit 2
3631 ! Safety threshold, lower limit of water output temperature
3632 ! Safety threshold, upper limit of water outlet temperature
Action
" Immediate shut down of compressors.
" Fault signalling.
If a DS50 is connected to the unit; Memorisation and diplay of all faults.
Otherwise; Memorisation and display only of the 3rd daily fault.
" Display of fault.
096, Lower limit.
097, Upper limit.
098, Insufficient water flow in condenser.
Reset
Automatic reset of the fault as soon as the temperature returns to the permitted operating range.
The fault will no longer be reset automatically after 3 cutouts in the same day and must be reset manually.
Note: The fault counter is cleared and reset every day at 11 am, provided the maximum number of faults has not
been reached.
Possible causes Solving the problem
Damaged probes or sensors Replace probe or sensor
Incorrect wiring or loose connection on a probe or sensor Check probe and sensor connections and wiring