Ambient Temperature and Humidity, Outside Limits
Error code: 013, 023, 032, 033
Description
The ambient temperature or humidity of the air measured by the sensor is outside the permitted range.
Lower limit of ambient temperature: Ambient temperature < safety threshold
Upper limit of ambient temperature: Ambient temperature > safety threshold
Lower limit of ambient humidity: Ambient humidity < safety threshold
Upper limit of ambient humidity: Ambient humidity > safety threshold
2112 ! Ambient temperature
3371 ! Safety threshold, lower limit of ambient temperature
3372 ! Safety threshold, upper limit of ambient temperature
2122 ! Ambient humidity
3378 ! Safety threshold, lower limit of ambient humidity
3379 ! Safety threshold, upper limit of ambient humidity
Action
" No safety.
" Fault signalling. Memorisation is displayed
" Display of fault.
013, Lower limit of ambient temperature.
023, Upper limit of ambient temperature.
032, Lower limit of ambient humidity.
033, Upper limit of ambient humidity.
Reset
Automatic resetting of fault as soon as the temperature or humidity returns within the permitted operating range.
Possible causes Solving the problem
Temperature probe or humidity sensor failed Replace probe or sensor.
Problem with wiring of probe or sensor Check the connections of the probe or sensor