CLIMATIC™50 – IOM – Rooftops/ Aircoolair CL50-ROOFTOPS-IOM-1107-E
33
Gas Burner Faults
Error code: 014, 015
Description
The gas burner control box has generated a fault and is no longer controlling the fume extractor fan.
Action
" The gas burner shuts down immediately.
" Fault signalling.
If a DS50 is connected to the unit; Memorisation and diplay of all faults.
Otherwise; Memorisation and display only of the 3rd daily fault.
" Display of fault.
014, 1st gas burner.
015, 2nd gas burner
Reset
The burner restarts automatically 2 minutes after safety setting by electrically resetting the burner control box.
The fault will no longer be reset automatically after 3 cutouts in the same day and must be reset manually.
Note: The fault counter is cleared and reset every day at 11 am, provided the maximum number of faults has not
been reached.
Possible causes Solving the problem
See IOM Flexy Read the documentation
Problem with the wiring of the gas burners Check the connections