FRESH AIR REHEATING SET POINT
Function
Climatic™ may be set to maintain a comfortable blowing temperature, by compensating the cold contribution of fresh air
in winter.
Description
If this function is activated:
• If the room temperature is in regulation dead zone, or heating mode, the blowing air regulation rule will maintain a
blowing temperature at least equivalent to the heating threshold.
• If the room temperature is in cooling mode, the minimum blowing temperature will be equal to the safety low limit
threshold plus 2K.
3331 ! Activation of the control of reheating of the fresh air, adjustment per zone.
HUMIDITY SET POINT (option)
Function
The relative humidity of room is maintained between two thresholds, a minimum threshold corresponding to the point of
humidification and a maximum threshold corresponding to the point of dehumidification.
Description
Dehumidification
It is ensured by the compressors in cooling mode.
It is active in the dead zone and cold mode of room temperature control.
Climatic™ gives priority to the temperature.
To ensure a complement of heating, the fresh air reheating set point must be activated.
Humidification
A signal 0-10v is generated proportionally to the regulation request.
3341 ! Dehumidification threshold - Relative humidity (%hr), adjustment by zone.
3342 ! Humidification threshold - Relative humidity (%Hr), adjustment by zone.
3358 ! Activation or inhibition, humidity control.