GAS BURNER TROUBLESHOUTING
If faults report ed on C LI MATI C
-Reset the CLIMATIC.
-Check v oltage: 230V after circuit breaker.
-Check GAS isolation shut-of f v a lv es are open.
-Check GAS pressure at the inlet of the GAS valves. It must be >20 mbar when the Burners shut down.
-Adjust the set points to priorities the burner. Increase the v alue of the room temperature set point to a temperature higher than
actual room temperature.
DIAGNOSTIC TABLE BALTIC GAS BURNER
STAGE
NORMAL
OPERATION
POSSIBLE
FAULT
ACTION POSSIBLE SOLUTION
Fault on the
blower
thermostat
+ Check connections on the blower
thermostat.
+ Replace thermostat
Lack of gas
supply
+ Check valv e’s opening & supply pressure + Restore gas supply
Heating
Requested
Extraction fans
start
Fault on the
superheat
thermostat on the
gas burner
support bar
+ Check superheat thermostat’s operation
after manual reset
+ Replace superheat
thermostat
After 10 seconds
safety shutdown
by the ignition
control block
+ Check connections of the control block on
the gas v alve
+ Repositioning of the
control block on the valve
+ Replace v alve
Starting of
the
extraction
fans
Extraction Fans
are running
Nothing happens
+ Check the free mov ement of the f an wheel
+ Check Electrical connection on the Gas
Ignition Control Block and on EF connection
Board
+ Check the Fan supply v oltage
+ Replace f an
+ Replace EF connection
board If necessary
Extraction
Fan is ON
After 30 to 45
seconds: pre-
ventilation the
fire-up
electrode
should spark.
Continuous
Ventilation
wit hout spark s
from fire-up
electrode
+ Check the fire-up electrode
+ Check the pressure drop at the pressure
switch: It must be higher than 165 Pa
+Check the good operation of the pressure
switch using an Ohmmeter and by artif icially
creating a depression in the tube.
+ Re-position the pressure
switch tube.
+ Change the pressure
switch.
After 4 seconds
the GAS Burner
still not operating
and saf ety
shutdown by the
Ignition Control
Block.
+ Check injection pressure during start -up
(Value f or High Heat)
+Remov e the control box from the gas
block.
+ Remove the air f rom the
Gas pipe-work
+ Adjust the injection
pressure to high heat
value.
+ Change the Control Box
if the Gas v alve is OK.
Continuous
ventilation
and sparks
from fire up
electrode.
After a f ew
seconds the
gas burner
fires-up
Within 4 seconds
the gas Burner
fires-up BUT
safety shutdown
from the Ignition
Control Block.
+ Check the Position and connection of the
Ionisation Probe. It must not be Earthed
(230V).
+ Measure the Ionisation Current: It must be
higher than 1.5 microAmps.
+ Check the Ty pe of GAS.
+Check the whole
electrical supply.
+ Adjust the supply and
injection pressure if g a s i s
different f rom natural gas
G20 :( G25 Gas of
Groningue f or example).
HEATING
: GAS BURNER

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox FLEXY II Series and is the answer not in the manual?

Lennox FLEXY II Series Specifications

General IconGeneral
BrandLennox
ModelFLEXY II Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals