EasyManua.ls Logo

Lenovo Neptune DWC RM100 - Page 31

Lenovo Neptune DWC RM100
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CDU Operating & Maintenance Guide Page 31
Neptune DWC RM100 in-rack Coolant Distribution Unit
Code
Description
Sev.
Self-clear
Latching
Shutdown
Delay
A06
T4 Secondary Temperature Sensor Fault
4
-
-
-
Detail:
Reading from Secondary return temperature sensor T4 is outside the normal range of 5 to 7C (41 to
165°F) or disconnected.
Action:
Check sensor connections to the control board, check in-line connections, replace sensor.
A07
T5 Primary Temperature Sensor Fault
4
-
-
-
Detail:
Reading from Primary return temperature sensor T5 is outside the normal range of 5 to 74°C (41 to
165°F) or disconnected.
Action:
Check sensor connections to the control board, check in-line connections, replace sensor.
A08*
RH Relative Humidity Sensor Fault
3
-
-
-
Detail:
Reading from Room humidity sensor RH is outside the normal range of 5 to 100% RH or disconnected.
[Note: if in Fixed Set Point + DW Offset mode, unit will revert to Fixed Set Point mode default 18°C
(6F)].
Action:
Check sensor connections to the control board, check in-line connections, replace sensor.
A9
PS1 Secondary Pressure Sensor Fault
3
-
-
-
Detail:
Reading from Secondary return pressure sensor PS1 (‘Fill’ pressure) is outside the normal range of -1
to 8 bar (-15 to 116 PSI) and min/max values only will be displayed. [Note: for DP control, if system
differential pressure is not valid, then pump speed will remain at last know demand].
Action:
Check sensor connections to the control board, check in-line connections, replace sensor.
A10
PS2 Secondary Pressure Sensor Fault
3
-
-
-
Detail:
Reading from Secondary filter outlet pressure sensor PS2 is outside the normal range of -1 to 8 bar (-
15 to 116 PSI) and min/max values only will be displayed [Note: if filter differential pressurePS1-PS2 is
not valid, then pump speed will remain at last know demand].
Action:
Check sensor connections to the control board, check in-line connections, replace sensor.
A11
PS3 Secondary Pressure Sensor Fault
2
-
-
-
Detail:
Reading from Secondary supply pressure sensor PS3 is outside the normal range of -1 to 8 bar (-15 to
116 PSI) and min/max values only will be displayed [Note: for DP control, if system differential
pressure PS3-PS1 is not valid, then pump speed will remain at last know demand].
Action:
Check sensor connections to the control board, check in-line connections, replace sensor.
A12
Secondary Flow Meter Sensor Fault
2
-
-
-
Detail:
Secondary flow meter output is below 4mA.
Action:
Check sensor connections to the control board, check in-line connections, replace sensor.
A13
Primary Flow Meter Sensor Fault
3
-
-
-
Detail:
Primary flow meter output is below 4mA.
Action:
Check sensor connections to the control board, check in-line connections, replace sensor.
A14
Micro SD Card Fault
3
-
-
-
Detail:
The SD card has either been removed or physically damaged.
Action:
Replace the SD card
A15
Leak Fault / Water Make-up Empty
2
-
-
-
Detail:
Fill pump has been running for more than 1 minute (default), when level sensor is made, but
minimum system pressure level has not been achieved. Also activated when level switch remains
open and system pressure has not been achieved (accompanied by an ‘A16 - Insufficient Water Level
alarm).
Action:
Check the make-up water container is full, tubes are free of air locks, container is properly connected
and fill pump is operational. Check system for leaks.

Table of Contents

Related product manuals