How to resolve secondary over pressure alarm on Lenovo Neptune DWC RM100?
- CCrystal RaymondAug 30, 2025
A secondary over pressure alarm on your Lenovo Server indicates that the pressure at PS3 has increased above the set value of 6Bar (87PSI). The most likely cause will be excessive heat build-up in the system, or a breach between the Primary and Secondary circuits within the plate heat exchanger. Check for High Temp alarms, relieve pressure at the drain point. Remove heat exchanger and replace.