EasyManua.ls Logo

Lenovo ThinkServer RS140 - Requirement for Batteries Containing Perchlorate; Particulate Contamination

Lenovo ThinkServer RS140
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Requirementforbatteriescontainingperchlorate
ThefollowingstatementappliestousersinthestateofCalifornia,U.S.A.
CaliforniaPerchlorateInformation:
Productscontainingmanganesedioxidelithiumcoincellbatteriesmaycontainperchlorate.
PerchlorateMaterial-specialhandlingmayapply,See
http://www.dtsc.ca.gov/hazardouswaste/perchlorate
Particulatecontamination
Attention:Airborneparticulates(includingmetalflakesorparticles)andreactivegasesactingaloneorin
combinationwithotherenvironmentalfactorssuchashumidityortemperaturemightposearisktothe
serverthatisdescribedinthisdocument.Risksthatareposedbythepresenceofexcessiveparticulate
levelsorconcentrationsofharmfulgasesincludedamagethatmightcausetheservertomalfunctionor
ceasefunctioningaltogether.Thisspecificationsetsforthlimitsforparticulatesandgasesthatareintended
toavoidsuchdamage.Thelimitsmustnotbeviewedorusedasdefinitivelimits,becausenumerous
otherfactors,suchastemperatureormoisturecontentoftheair,caninfluencetheimpactofparticulates
orenvironmentalcorrosivesandgaseouscontaminanttransfer.Intheabsenceofspecificlimitsthatare
setforthinthisdocument,youmustimplementpracticesthatmaintainparticulateandgaslevelsthatare
consistentwiththeprotectionofhumanhealthandsafety.IfLenovodeterminesthatthelevelsofparticulates
orgasesinyourenvironmenthavecauseddamagetotheserver,Lenovomayconditionprovisionofrepair
orreplacementofserversorpartsonimplementationofappropriateremedialmeasurestomitigatesuch
environmentalcontamination.Implementationofsuchremedialmeasuresisacustomerresponsibility.
Table4.Limitsforparticulatesandgases
ContaminantLimits
Particulate
Theroomairmustbecontinuouslyfilteredwith40%atmosphericdustspotefficiency
(MERV9)accordingtoASHRAEStandard52.2
1
.
Airthatentersadatacentermustbefilteredto99.97%efficiencyorgreater,using
high-efficiencyparticulateair(HEPA)filtersthatmeetMIL-STD-282.
Thedeliquescentrelativehumidityoftheparticulatecontaminationmustbemorethan60%
2
.
Theroommustbefreeofconductivecontaminationsuchaszincwhiskers.
GaseousCopper:ClassG1asperANSI/ISA71.04-1985
3
Silver:Corrosionrateoflessthan300Åin30days
1
ASHRAE52.2-2008-MethodofTestingGeneralVentilationAir-CleaningDevicesforRemovalEfficiencybyParticle
Size.Atlanta:AmericanSocietyofHeating,RefrigeratingandAir-ConditioningEngineers,Inc.
2
Thedeliquescentrelativehumidityofparticulatecontaminationistherelativehumidityatwhichthedustabsorbs
enoughwatertobecomewetandpromoteionicconduction.
3
ANSI/ISA-71.04-1985.Environmentalconditionsforprocessmeasurementandcontrolsystems:Airborne
contaminants.InstrumentSocietyofAmerica,ResearchTrianglePark,NorthCarolina,U.S.A.
124ThinkServerRS140UserGuideandHardwareMaintenanceManual

Table of Contents

Other manuals for Lenovo ThinkServer RS140

Related product manuals