Configuration
7-132
48XX/49XXSHB0399
Code Possible settingsNameCode
InfoSelectionLenze
Name
C123 Current
threshold for
blocking
protection for
C124
0.95
I
rated
0 A {0.1A} 100 A
100 A {1 A} 3600 A
Rated current depends on the controller:
0 ... 87A (4902)
0 ... 135A (4903)
0 ... 270A (4904)
0 ... 450A (4905)
0 ... 720A (4906)
0 ... 900A (4907)
0 ... 1200A (4X08)
0 ... 1800A (4X09)
0 ... 2520A (4X11)
0 ... 3600A (4X12)
0 ... 4050A (4X13)
See motor nameplate
C124* Blocking time 60 s 1 s {1 s} 100 s Motor standstill time until TRIP is set
C125*¤ Change of baud
rate for
interface
0 -0- 9600 baud
-1- 4800 baud
-2- 2400 baud
-3- 1200 baud
C126* Delay
(Monitoring ser.
interface)
3000 s 0.2 s {0.1 s} 10 s
10 s {1 s} 100 s
100 s {10 s} 3600 s
C128* Delay for C116 0.000 s 0.000 s {0.001 s} 240.000 s Signal delay times for FDO 1...5 and relay
output.
C130* Enable
additional T
i
times
0 -0- T
ir
(C012) / T
if
(C013) active
-1- T
ir1
/T
if1
active
...
-15- T
ir15
/T
if15
active
If the T
i
times are enabled via terminal,
C130 is for display only.
C131*¤ Ramp function
generator STOP
0 -0- Enable ramp function generator
-1- Stop ramp function generator
If ramp function generator STOP (main
setpoint) is enabled via terminal, C131 is
for display only.
C132*¤ Ramp function
generator input
=0
0 -0- Enable mains setpoint at RFG input
-1- Ramp function generator input = 0
[C134*] Ramp function
generator
characteristic
0 -0- linear characteristic
-1- S-shaped characteristic
C136* FDI state Bit Free digital input
0FDI1
...
3FDI4
4FDI5
Only readable via LECOM. C136 indicates
the states of the digital inputs as a
decimal or binary value.The change of
polarity under C114 is considered in
C136.