Technical Data
3-8 821XKlimaBA0399
3.4.2 Single drives with 150 % overload
The table values are valid for the operation of 82XX controllers as
single drives with a matching motor and 150 % overload.
Type
Mains input L1, L2, L3, PE/motor connection U, V, W, PE
T
p
e
Operation without mains filter/mains choke Operation with mains filter/mains choke
Fuse
F1, F2, F3
E.l.c.b. Cable
cross-section
1)
Fuse
F1, F2, F3
E.l.c.b. Cable
cross-section
1)
VDE UL VDE mm
2
AWG VDE UL VDE mm
2
AWG
8211 M6A - B6A 1 17 M6A - B6A 1 17
8212 M 10A - B6A 1.5 15 M6A - B6A 1 17
8213 M 10A - B 10A 1.5 15 M 10A - B 10A 1.5 15
8214 - - - - - M10A - B 10A 1.5 15
8215 M 16A - B 16A 2.5 13 M 16A - B 13A 2.5 13
8216 M 25A - B 25A 6 10 M 20A - B 20A 4 11
8217 M 32A - B 32A 6 10 M 25A - B 25A 6 10
8218 - - - - - M32A - B 32A 6 10
1)
Observe national and regional regulations (e. g. VDE/EVU)!