Installation
8250BA0903 4-5
4.2.2 Protection of the brake unit
Stop!
The brake units contain electrostatically sensitive components.
Prior to assembly and service operations, the personnel
must be free of electrostatic charge:
- They can discharge themselves by touching the PE
fixing screw or another grounded metal part in the
control cabinet.
In the event of condensation connect the brake unit to
mains voltage only after the visible humidity has
evaporated.
4.2.3 Specification of cables used
The cables used must comply with the approvals required
atthesite(eg.UL).
The prescribed minimum cross-sections of PE conductors
must be maintained in all cases. The cross-section of the
PE conductor must be at least as large as the
cross-section of the power connections (VDE 0160).
The screening quality of a cable is determined by
- a good screen connection
- a low screen resistance
Use only screens with tin-plated or nickel-plated copper
braid!
Screens of steel braid are not suitable.
- the degree of coverage of the screen braid:
at least 70% to 80% with a coverage angle of 90°
Note!
The screens are only required to comply with existing standards
(e.g. VDE 0160, EN 50178).