Installation
4-6 8250BA0903
4.3 Connection
4.3.1 Power connection
All indications about cable cross-sections are
recommendations and refer to the application:
- in control cabinets and machines
-incableducts
- at a max. ambient temperature +40 °C
The compliance with other standards (e.g.: VDE 0113, VDE
0289, etc.) remains the responsibility of the user.
The cables between brake unit and controller must not be
longer than max. 2 m.
If the brake unit is directly connected with the controller
and the cable length does not exceed £ 0.5 m, the cables
can be used as unscreened single cores.
For a radio interference suppression (limit-value class A or
B) to DIN 55011 observe the following:
- The cables must be screened.
- For cable lengths up to 1 m it is sufficient to connect the
screen at the middle.
- For cable lengths > 1 m, the screen must always be
connected on both sides.
Connection
The cables between controller and brake unit must be
DC-bus connected to the terminals +UG, -UG.
Observe stud torques:
Terminals
0.5 ... 0.6 Nm
e
a
s
4.4 ... 5.3 lbfin