Commissioning
Linear V/f-characteristic control
T
EDK82MV222 DE/EN/FR 9.0
NNP
L
10. Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
f
[ H z ]
f
2
C 0 0 1 1
f
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
= t
ir
C0011
f
2
f
1
t
ir
= acceleration time
wanted
11. Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
= t
if
C0011
f
2
f
1
t
if
= deceleration time
wanted
12. Set the V/f-rated frequency
(C0015)
Lenze setting: 50.00 Hz
NMMB
M
M `MMNR
s
ãáå
s
çìí
Ñ
13. Set the V
min
boost (C0016)
Lenze setting: Depends on the
controller type
The Lenze setting is
suitable for all common
applications
14. If you want to change other
settings,pleasegotothe
ALL
menu
Activate e.g. JOG frequencies
(C0037, C0038, C0039) or motor
temperature monitoring (C0119)
15.
Go to the ALL menu
A Check the fan monitoring
setting under code C0608:
for 8200 motec 0.25...0.37
kW and 0.55...2.2 kW:
C0608 = 0! (default setting)
for 8200 motec 3...7.5 kW:
C0608 =1 (recommended)
or C0608 = 2!
Stop!
Function must be
activated during
commissioning!
Otherwise, the
controller may be
destroyed through
overheating!
for all other controllers:
C0608 = 0 ! (default
setting)
B Select additional functions via
codes, if necessary.
When all settings are complete:
16. Select the setpoint E.g. via potentiometer at
terminals7,8,9
17. Enable the controller
20
28
X3
misc002
Terminal X3/28 = HIGH