EasyManua.ls Logo

Lenze ECS series - Page 121

Lenze ECS series
483 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
Setting of the feedback system for position and speed control
TTL/SinCos encoder as position encoder and resolver as speed encoder
6
121
EDBCSXA064 EN 3.2
IMPORTANTPossible settingsCode
SelectionLenze/
{Appl.}
DesignationNo.
[C0420] Encoder const. 512
Number of increments of the
encoder
331
115
122
1 {1 inc/rev} 8192 Sets C0419 = 0 ("common") if the
value is altered.
[C0421] Encoder volt 0
Encoder voltage
331
115
122
0 5.0 V
Sets C0419 = 0 ("common") if the
value is altered.
1 5.6 V
2 6.3 V
3 6.9 V
4 7.5 V
5 8.1 V
[C0427] Enc. signal 0
Function of the master frequency
input signals on X8 (DFIN)
331
115
122
0 2−phase
1 A: speed
B: direction
2 A or B: speed or direction
[C0491] X8 in/out 0
Function of X8
331
115
122
0 X8 is input
1 X8 is output

Table of Contents

Other manuals for Lenze ECS series

Related product manuals