Appendix
Code list
11
151
EDBCSXE040 EN 6.0
Parameter
C0579
Designation
Response − monitoring of internal brake resistor (OC6)
Data type: INTEGER_32
Index: 23996
dec
= 5DBC
hex
Monitoring response of the internal brake resistor (fault message OC6)
116
Selection list (Lenze setting printed in bold) Information
0 TRIP
3 No response
Parameter
C0595
Designation
Response − bus−off/toggle bit monitoring (CE4)
Data type: INTEGER_32
Index: 23980
dec
= 5DAC
hex
Bus−off/toggle bit monitoring response of the CAN bus (fault message CE4)
118
Selection list (Lenze setting printed in bold) Information
0 TRIP
3 No response
Parameter
C0599
Designation
Delay time − system disturbance (LP1)
Data type: INTEGER_32
Index: 23976
dec
= 5DA8
hex
If an LP1 warning or LP1 message is active for the set time, an LP1−TRIP is enabled.
l Value < 65535 ms: LP1−TRIP
l Value = 65535 ms: LP1 warning/LP1 message
113
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 65535 ms
Parameter
C0866
Designation
Process data input words CAN1_IN
Data type: UNSIGNED_16
Index: 23709
dec
= 5C9D
hex
If the system bus (CAN) is in the "Operational" state, you can check the contents of the data words received via
CAN1_IN via C0866 (subcodes 1 and 2).
l The value is bit coded.
Display range (min. value | unit | max. value)
0x0000 0xFFFF
Subcodes Information
C0866/1 CAN1_IN.W0 (word 1, control word "Ctrl1")
C0866/2 CAN1_IN.W1 (word 2)
Parameter
C0868
Designation
Process data output words CAN1_OUT
Data type: UNSIGNED_16
Index: 23707
dec
= 5C9B
hex
If the system bus (CAN) is in the "Operational" state, you can check the contents of the data words sent via
CAN1_OUT via C0868 (subcodes 1 and 2).
l The value is bit coded.
Display range (min. value | unit | max. value)
0x0000 0xFFFF
Subcodes Information
C0868/1 CAN1_OUT.W0 (word 1, status word 1 "Stat1")
C0868/2 CAN1_OUT.W1 (word 2, status word 2 "Stat2")