Electrical installaon
Operang Instrucons i550 protec 11
6.3 Control terminals
Control terminals
Standard I/O
Input/output Terminal X3 Informaon
Digital inputs DI1, DI2, DI3,
DI4, DI5
DI3/DI4 can be oponally used as frequency or encoder input.
HIGH-acve/LOW-acve switchable
LOW = 0 ... +3 V,
HIGH = +12 V ... +30 V
Digital outputs DO1 Digital output (max. 100 mA for DO1 and 24-V output)
Analog inputs AI1, AI2 Can be oponally used as voltage input or current input.
Analog outputs AO1 Can be oponally used as voltage output or current output.
24-V input 24E Input for mains-independent power DC supply of control electronics
(including communicaon). Max. 1 A
10-V output 10 V Primarily for the supply of a potenometer (1 ... 10 kΩ).
Max. 10 mA
24-V output 24 V Primarily for the supply of digital inputs.
(Max. 100 mA for DO1 and 24-V output)
Reference potenal GND
Connecon system Spring terminal
Rated power
hp 0.5 ... 15
kW 0.37 ... 11
Connecon Control terminals X3
Connecon type Spring terminal
Max. cable cross-secon AWG 16
Stripping length in 0.35
Tightening torque lb-in -
Tools required 3/32 x 0.02
6.4 Relay output
The relay is not suitable for direct switching of an electromechanical
holding brake.
Use a corresponding suppressor circuit in case of an inducve or
capacive load.
Rated power
hp 0.5 ... 15
kW 0.37 ... 11
Connecon Relay output X9
Connecon type Screw terminal
Max. cable cross-secon AWG 16
Stripping length inch 0.24
Tightening torque lb-in 1.8
Tools required 3/32 x 0.02
COM Common contact
NC Normally-closed contact
NO Normally-open contact
Max. switching voltage/switching
current
AC 240 V/3 A
DC 24 V/2 A
DC 240 V/0.16 A
6.5 PTC input
In the default seng, the motor temperature monitoring is acve!
By default, a wire jumper is installed between the terminals T1 and T2.
Before connecng a thermal sensor, remove the wire jumper.
Rated power
hp 0.5 ... 15
kW 0.37 ... 11
Connecon PTC or
thermal contact X109
Terminal T1
Terminal T2
Sensor types PTC single sensor
PTC triplet sensor
Thermal contact
Relay output
NC
NO
COM
X9
AC 240 V
3 A
PTC input
X109
T1
T2