Electrical installaon
Operang Instrucons i550 protec12
6.6 1-phasemainsconnecon120V
Terminal data, 1-phase 120 V
Inverter I55APxxxA
Rated power
hp 0.5 ... 1.5
kW 0.37 ... 1.1
Connecon X100 PE
X105
Connecon type Screw terminal PE screw
Screw
terminal
Max. cable cross-secon AWG 10 16 10
Stripping length in 0.35 0.4 0.35
Tightening torque lb-in 4.4 18 4.4
Tools required 0.6 x 3.5 Torx 20 0.6 x 3.5
Fusing data
Rated power
hp 0.5 1 1.5
kW 0.37 0.75 1.1
Operaonwithoutmainschoke
Rated mains current A 9.6 16.8 22.9
Output tated current (8 kHz) A 2.4 4.2 6
Fuse
SCCR kA 5 5 5
Characterisc all acc. to UL248/Class CC, CF, J, T
Max. rated current A 32 32 32
Circuit breaker
SCCR kA 5 5 5
Characterisc all acc. to UL 489
Max. rated current A 32 32 32
Earth-leakage circuit breaker
1-phase mains connecon ≥30 mA, type B
Mainsconnecon
PE
N
L2
Motorconnecon
X105
U
V
W
Rb1
Rb2
M
3~