Electrical installation
Important notes
Motor protection
6
l
88
EDS700ACBA EN 5.1
ƒ In case of condensation, do not connect the controller to the mains voltage before
the moisture has evaporated completely.
ƒ Provide unused control inputs and outputs with terminal strips.
6.1.3 Motor protection
ƒ Extensive protection against overload by means of temperature monitoring:
with KTY or PTC sensors of the resolvers or encoders
with activated I
2
t monitoring
Combination of the possible monitoring modes
ƒ Only use motors which have a suitable insulation for the inverter operation:
Insulation resistance: min. û = 1.5 kV, min. du/dt = 5 kV/ms
When using motors with an unknown insulation resistance, please contact your
motor supplier.
6.1.4 Interaction with compensation equipment
ƒ Drive control systems only consume very little fundamental reactive power from the
supplying AC system. Therefore, compensation is not required.
ƒ If the drive control systems are operated on supply systems by means of
compensation equipment, the compensation equipment must include chokes.
For this purpose, please contact the supplier of the compensation equipment.