Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
Installation in the control cabinet
6
l
98
EDS700ACBA EN 5.1
Continuation of cable routing
Separation of the "hot" motor cable from the control, signal, and mains cables:
ƒ Never install motor and signal cables in parallel and only cross at right angles
ƒ The cables of a 24 V power supply unit (plus and minus cable) must be installed
closely together over their entire length in order that no loops may occur.