4 Technical data
General data and operating conditions
4.1 General data and operating conditions
General data
Conformity and approval
Conformity
CE 2004/108/EC EMC Directive
EAC TP TC 020/2011 Electromagnetic Eurasian Conformity
(TR CU 020/2011)
compatibility of technical
TR CU: Technical Regulation of
means
Customs Union
Other
RoHS
_________________
2011/65/EU
________
Products are lead-free acc. to directive.
Protection of persons and device protection
Enclosure
Front panel EN 60529 IP65
Rear panel EN 60529 IP20
Electrical isolation
To the fieldbus yes
To the process level None
Protective measures Against short circuit
EMC
Interference emission EN 61000-6-4 Class A (industrial premises)
Noise immunity EN 61000-6-2
Industrial premises
EN 61000-4-2 ESD; severity 3, i.e.
Air discharge: 8 kV,
4 kV with contact discharge
EN 61000-4-3 RF interference (housing)
80 MHz ... 1000 MHz, 10 V/m 80 % AM
(1 kHz)
EN 61000-4-4 Burst, severity level 3
EN 61000-4-5 Surge, severity 1
EN 61000-4-6 RF cable-guided
150 kHz ... 80 MHz, 10 V/m 80 % AM
(1 kHz)
Operating conditions
Ambient conditions
Climatic
Storage/transport EN 60721-3-2 2K3:
-25 ... +70 °C depending on the air humidity
(see diagrams Ш 21)
Operation EN 60721-3-2 3K3:
0 ... +50 °C depending on the air humidity
(see diagrams Ш 21)
Air humidity EN 60721-3-3 3K3 (without condensation, relative humidity 10 ... 95 %)
Pollution EN 61131-2 Pollution degree 2
Mechanical
Vibration EN 61131-2
1 g
Shock EN 61131-2
15 g
Site altitude
Operation < 2000 m amsl
20