EasyManua.ls Logo

Lenze SM302 - Page 26

Lenze SM302
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety engineering
Device modules
Mission time
1
26
EDS94AYAF EN 1.0
1.2.4.2 Commissioning
ƒ For commissioning and safe parameter setting, the Lenze »Engineer« PC
software from version 02.23 must be used.
If you select the safety module in the Project view, various tabs are available in the
Operating rangevia which the safety module can be parameterised. In all other
program parts the parameters of the safety module can only be read. Thus, the write
access of these parameters (codes) is marked with .
ƒ Settings in or at the module:
Safety address
Safe parameter setting of the functions to be used
ƒ Required settings in the basic device:
C00214, type of safety module
Implementation of the SM302 into the drive application by evaluating the control
information and status information.
ƒ During commissioning and after the replacement of a module it is vital to check the
safety function. Additional information contains the "Acceptance" chapter. ( 71).