Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES 11
Installation
Terminal Data for control connections (printed in bold = Lenze setting)
7
Reference common
8
Analog input
0 … 10 V (changeable under C34)
input resistance: >50 k
(with current signal: 250 Ω)
9
Internal DC supply for setpoint potentiometer +10 V, max. 10 mA
20
Internal DC supply for digital inputs +12 V, max. 20 mA
28
Digital input Start/Stop
LOW = Stop; HIGH = Run Enable
input resistance = 3.3 k
E1
DigitalinputcongurablewithCE1
Activate fixed setpoint 1 (JOG1)
HIGH = JOG1 active
Both HIGH = JOG3 active
R
i
= 3.3 k
E2
DigitalinputcongurablewithCE2
Activate fixed setpoint 2 (JOG2)
HIGH = JOG2 active
E3
DigitalinputcongurablewithCE3
Activate DC injection brake (DCB)
HIGH = DCB active
K14
Relay output (N.O. contact)
congurablewithC08
Fault (TRIP)
AC 250V / 3A
DC 24V / 2A ... 240V / 0.22A
K12
LOW = 0 … +3 V, HIGH = +12 … +30 V
Protection against contact
•Allterminalshaveabasicisolation(singleinsulatingdistance)
•Protectionagainstcontactcanonlybeensuredbyadditionalmeasures(i.e.doubleinsulation)
3.2.4 Control terminals