INSTALLATION PLACES
INSTALLATION PLACES
Install the air conditioner in the location that satisfies the following conditions.
- The place shall easily bear a load exceeding four times the indoor unit’s weight.
- The place shall be able to inspect the unit as the figure.
- The place where the unit shall be leveled.
- The place shall allow easy water drainage.
(Suitable dimension “H” is necessary to get a slope to drain as figure.)
- The place shall easily connect with the outdoor unit.
- The place where the unit is not affected by an electrical noise.
- The place where air circulation in the room will be good .
- There should not be any heat source or steam near the unit.
Ceiling Concealed Duct – Low Static Ceiling Concealed Duct – Mid Static
Inspection hole (600 x 600)
Control box
H=20 or more
• Suitable dimension "H" is necessary to get a slope
  to drain as shown in the figure
600
600
Air outlet
Air outlet
Top view
(unit: mm)
Front view
Inspection hole
(600 x 600)
Control box
1000
H
600
600
Front
Top view
(unit: mm)
(unit: mm)
Side view
CAUTION
• In case that the unit is installed near the sea, the installation parts may be corroded by salt,
The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
!
[Inspection Hole Standard]
Number of 
Inspection hole
Distance between 
False ceiling & Actual ceiling
Remarks
1 More than 100cm Sufficient space in the ceiling for servicing. 
2 20cm to 100cm Insufficient space. Difficult for servicing
Hole size should be
more than the size
of IDU.
Less than 20cm Minimum height for motor replacement.