EasyManua.ls Logo

LG CL09R.N20 - Page 36

LG CL09R.N20
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
HOW TO SET E.S.P?
ENGLISH
Ceiling Concealed Duct – Mid static
Table 2
Model Step CMM
Static Pressure[mmAq(Pa)]
2(20) 2.5(25) 3(29) 4(39) 6(59) 8(78) 10(98) 12(118) 13(127) 14(137) 15(147)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
CM18R.N10
LOW 13 73 74 77 88 93 103 111 117 120 125 128
MID 14.5 76 77 85 91 97 107 114 121 125 128 131
HIGH 16.5 85 87 90 94 103 110 118 125 128 131 134
CM24R.N10
LOW 14.5 76 77 85 89 97 106 114 121 124 127 132
MID 16.5 85 87 90 94 103 111 118 125 128 131 136
HIGH 18 90 92 95 99 108 115 122 129 132 135 138
Model Step CMM
Static Pressure[mmAq(Pa)]
2.5(25) 4(39) 5(49) 6(59) 7(69) 8(78) 9(88) 10(98) 11(108) 13(127) 15(147)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
UM30R.N10
LOW 18 96 102 107 110 114 118 122 125 127 130 132
MID 20 102 110 114 118 121 125 127 130 133 134 136
HIGH 22 110 117 121 124 127 130 133 136 137 138 140
Model Step CMM
Static Pressure[mmAq(Pa)]
4(39) 5(49) 6(59) 7(69) 8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 15(147)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
UM36R.N20
LOW 24 88 91 95 100 101 108 113 115 118 121 128
MID 28 93 97 101 105 108 115 118 120 124 127 134
HIGH 32 101 105 109 112 115 119 123 126 128 133 137
1,MFL67939930,영영 2018. 3. 16. 영영 2:25 Page 36