ELECTRICAL CONNECTIONS | 85
Electrical Connections
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
Figure 23: Example of a Typical Heat Recovery Operation Power Wiring and Communications Cable Schematic.
WARNING
Heat Recovery Unit
3(A) 4(B)
A B 3(A) 4(B)
B
ODU IDU CENTRAL DRY1 DRY2 GND 12 V
AB
A
BA
B
DRY1 DRY2 GND 12 V
AB
A
BA
B
DRY1 DRY2 GND 12 V
ABA
B
A
Heat Recovery Operation
Communications Cable Between Master Outdoor Unit and
Heat Recovery Units / Indoor Units
Communications Cable Between Master Outdoor Unit and Slave Outdoor Unit(s)
B
ODU IDU
CENTRAL
DRY1 DRY2 GND 12V
AB
A
BA
Master
Outdoor Unit Communication Terminal Block
Master
Outdoor Unit Communication Terminal Block
Slave 1
Outdoor Unit Communication Terminal Block
Slave 2
Outdoor Unit Communication Terminal Block
Indoor Unit Indoor Unit
ODU IDU CENTRAL
ODU IDU CENTRAL
Switch
Communication Line
(2-wire Cable)
Power Line
(3-wire Cable)
Communication Line
(3-wire Cable)
Power Line
(2-wire Cable)
Power Line
(2-wire Cable)
Power Line
(2-wire Cable)
Power Line
(2-wire Cable)
Master
Indoor Units
Power supply
3 Phase 3 Wires
60Hz 208-230V or
60Hz 460V
Power supply
1 Phase 60Hz
208-230V
Main Switch
Slave1 Slave2
Switch Switch
Pull box
(Installer
option)
Pull box
(Installer
option)
Pull box
(Installer
option)
Power Line
(2-wire Cable)
HR unit
R(L1) S(L2) T(L3 R) (L1) S(L2) T(L3 R) (L1) S(L2) T(L3)
L1 L2
Fused
Disconnect
Fused
Disconnect
Fused
Disconnect
Disconnect
SYSTEM FOR HEAT RECOVERY
OPERATION, 208-230V AND 460V
• Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise, and
motor current leakage. 'RQRWFRQQHFWWKHJURXQGOLQHWRWKHSLSHV7KHUHLVULVNRI¿UHHOHFWULFVKRFNH[SORVLRQSK\VLFDOLQMXU\RUGHDWK
• Install a main shutoff switch that interrupts all power sources simultaneously. There is risk of fire, electric shock, explosion, physical injury
or death.
• Communication cable between Master ODU to Slave ODU(s), and Master ODU to IDUs / HRUs to be 18 AWG, 2-conductor, twisted, strand-
ed, shielded. Ensure the communication cable shield is properly grounded to the Master ODU chassis only.
Do not ground the ODU to
IDUs / HRUs communication cable at any other point. Wiring must comply with all applicable local and national codes. Inadequate connec-
tions may generate heat, cause a fire, and physical injury or death.
• The GND terminal at the main PCB is a negative terminal for dry contact, not a ground. Inadequate connections may generate heat, cause
a fire, and physical injury or death.
• Make sure that the terminal numbers of master outdoor unit and slave outdoor unit(s) match (A to A, B to B). The system will malfunction if
not properly wired.
• Maintain polarity throughout the communication network. The system will malfunction if not properly wired.
• If the system operates in reversed phase, it may break the compressors and other components.
• If there is a possibility of reversed phase, phase loss, momentary blackout, or the power goes on and off while the system is operating, install
D¿HOGVXSSOLHGSKDVHORVVSURWHFWLRQFLUFXLW2SHUDWLQJWKHV\VWHPLQUHYHUVHSKDVHPD\EUHDNWKHFRPSUHVVRUDQGRWKHUXQLWFRPSRQHQWV