67
Troubleshooting
Due to our policy of continuous product innovation, some specifications may change without notification.  
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Error Codes
• Indicate different types of unit failures, assist in self-diagnosis and to track the frequency 
of occurrence.
• Error codes are shown on the LED of indoor units, wired remote controller, the outdoor 
XQLWFRQWUROERDUGDQGRQWKHPDLQVFUHHQRIWKH/*0RQLWRULQJ9LHZ/*09'LDJQRVWLF
Software. 
• ,IWZRRUPRUHHUURUVRFFXUVLPXOWDQHRXVO\WKHORZHUHUURUFRGHQXPEHULVGLVSOD\HG¿UVW
• After error is resolved, the error code does not display.
(UURU'LVSOD\
The first, second, and third number on the LED 
indicates error number; the fourth number on 
LED indicates outdoor unit number.
Examples: 211 = Error No. 21 on master unit, 
213 = Error No. 21 on slave2 unit, 21051 = Error 
No. 105 on master unit.  
(UURU&RGH1RPHQFODWXUH'HILQLWLRQV
• 0,&201RQYRODWLOHPHPRU\FKLSZKHUHXQLW
setup information is stored.
• (35201RQYRODWLOHPHPRU\FKLSZKHUH
device identification, size, and factory defined 
default component operating parameters are 
stored.
ERROR CODE TABLES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service 
troubleshooting of the Multi V S product.
2 1  1 c 1  1
Repeats
Compressor Error
Error No.
Unit
Error No. of Unit
([DPSOH
Error Code 'HVFULSWLRQ 'HWDLOV
Indoor Unit
01-
Indoor unit return air or optional remote wall tempera-
ture sensor communications error.
Indoor unit air temperature sensor has disconnected or short 
circuited. (Check the wiring, connection at the CN Room socket 
on the indoor unit PCB, then check the thermistor.)
02-
Indoor unit inlet pipe temperature sensor communica-
tion error.
Indoor unit inlet pipe temperature sensor has disconnected or 
short circuited. (Check the connection at the CN-PIPE/IN socket 
on the indoor unit PCB, then check the thermistor.)
03-
Communication error between zone controller and 
indoor unit.
Indoor unit PCB has not received communications signal from 
zone controller.
0 4 - Indoor unit drain pump error.
Drain pump and/or flow switch is/are malfunctioning. Also check 
drain line for obstructions.
05-
Communication error between outdoor unit and indoor 
unit.
• Indoor unit has not received communications signal from out-
door unit. 
• Check indoor unit to outdoor unit communication cable connec-
tions for issues.
0 6 - Indoor unit outlet pipe temperature sensor error.
Indoor unit outlet pipe temperature sensor has disconnected or 
short circuited. (Check the connection at the CN-PIPE/OUT sock-
et on the indoor unit PCB, then check the thermistor.)
09-,QGRRUXQLW(3520HUURU
• Communication error between the indoor unit PCB board and its 
RSWLRQFDUG7KHRSWLRQFDUGLVDERXWƍ[ƍDQGLVSOXJJHGLQWR
the indoor unit PCB board. Check connection between the two.)
• &RPPXQLFDWLRQHUURUEHWZHHQ(3520FKLSVRQLQGRRUXQLW
main PCB.
• ,QGRRUXQLW(3520GDWDLVQRWDYDLODEOH
1 0 - Indoor unit BLDC fan motor communications error.
• )DQPRWRUKDVEHHQUHPRYHGRULVGHIHFWLYH8VHWKH2+0DQG
voltage check charts in the product service manual.
• The system has detected the fan motor is not spinning. 
• On new installs, verify installation manual and paperwork were 
removed from fan discharge shroud before unit was installed. 
• &KHFNWKHZLULQJSOXJDQGFRQQHFWLRQDWVRFNHWV&102725
DQG&102725LIXVHG
Outdoor Unit
2110DVWHURXWGRRUXQLWinverter compressor PCB error.
• Outdoor unit inverter compressor PCB error. 
• Under voltage
• 5HIULJHUDQWÀRZUHVWULFWLRQIURPGHIHFWLYH/(9
• Refrigerant charge is too high (overcharge). 
Table 46: Indoor Unit Error Codes.
For detailed information on how to troubleshoot each error, see the Multi V S Service Manual on www.lg-vrf.com.