MULTI V Water IV System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Zone Setting
1. Set the address of the heat recovery control unit valve to the central control address of the connected indoor unit.
SW01M: Selects the valve to address.
SW03M: Increases the ten (10) digit of the valve address.
SW04M: Increases the valve address by one (1).
SW05M: Rotary switch.
2. Prerequisite for manual valve addressing: The central control address of each indoor unit must be preset at its wired remote controller.
Dip Switch No. Setup
No. 1 Manual addressing valve No. 1
No. 2 Manual addressing valve No. 2
No. 3 Manual addressing valve No. 3
No. 4 Manual addressing valve No. 4
SW03M Increases the ten (10) digit of the valve address
SW04M Increases the valve address by one (1)
SW05M Manual addressing zoned indoor units
SW01M
SW03M
SW04M
SW05M
0
ON
OFF
Table 72:Zone Setting.
PRE-COMMISSIONING
Setting up the Heat Recovery Unit (Heat Recovery Systems Only)