Table 47: Heat Pump Triple-Frame Connection Pipe Sizes.
Figure 36: Heat Pump Triple-Frame Refrigerant Pipe Connections.
REFRIGERANT PIPING INSTALLATION
Pipe Sizing for ARWN Series Heat Pump Systems
Triple-Frame Heat Pump Water Source Unit Connections
WSU
System Size
(tons)
WSU System
Model
Master Frame Slave 1 Frame Slave 2 Frame
B Pipe (in. OD)
If Equivalent Pipe
Length from WSU to
Farthest IDU is <295 ft.
B Pipe (in. OD)
If Equivalent Pipe
Length from WSU to
Farthest IDU is ≥295 ft.
Liquid Vapor Liquid Vapor
30 ARWN360BAS4 ARWN144BAS4 ARWN144BAS4 ARWN072BAS4 3/4 1-3/8 7/8 1-5/8
36 ARWN432BAS4 ARWN144BAS4 ARWN144BAS4 ARWN144BAS4 3/4 1-3/8 7/8 1-5/8
40 ARWB480DAS4 ARWB192DAS4 ARWB144DAS4 ARWB144DAS4 3/4 1-3/8 7/8 1-5/8
48 ARWB576DAS4 ARWB192DAS4 ARWB192DAS4 ARWB192DAS4 3/4 1-3/8 7/8 1-5/8
Note:
Larger-capacity water source units must be the master in a multi-frame system.
Master water source unit capacity must be greater than or equal to the Slave 1 water source unit
capacity, and, where applicable, Slave 1 water source unit capacity must be greater than or equal
to Slave 2 water source unit capacity.
Be sure to insulate all refrigerant system piping and piping connections.
Refrigerant Pipe Sizes for WSU Connections
Figure 36 is for reference only, is not to scale, and does not represent required pipe routing.
Multi-frame Y-branches MUST be installed horizontally as shown in Figure 22.
A1, A2, and A3 pipe diameters match the water source unit connection diameters.
Main pipe C diameters are sized by LATS.
See Table 47 for B pipe diameters.
Slave 2
Slave 1
Master
To Indoor Units
A1
A2
ARCNN21 Kit
Two (2) Y-branches
for liquid pipe and vapor pipe
B
A3
C – Main Pipe Sized by LATS
Liquid Pipe
Vapor Pipe
Not Used
for HP
Liquid Pipe
Vapor Pipe
Liquid Pipe
Vapor Pipe
ARCNN21 and ARCNN31
Multi-Frame WSU
Heat Pump Systems
Y-Branch Connector Kits
Liquid Pipe
Vapor Pipe
Represents TWO pipes: Liquid and Vapor
ARCNN31 Kit
Two (2) Y-branches
for liquid pipe and vapor pipe