Electrical System Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Communication Cable Between the Indoor Units and the
Wall-Mounted Zone Controller
Communication Cable Between Multiple Indoor Units
Operating as a Group (Group Control)
Use only LG-provided three-conductor communications cable between the indoor unit and the
wall-mounted zone controller.
NEVER splice, cut, or extend cable length with field provided cable. If the length must be extended,
use the LG Extension Kit (sold separately). A maximum of four (4) kits (up to 165 feet) can be
connected together.
Set the indoor unit operating parameters with DIP switches on the indoor unit control PCB or by
setting the zone controller. Refer to the indoor unit installation manuals for details.
If any indoor units operate as a group, use one (or multiple)
three-core Group Control Kit (sold separately) containing
extension and Y-splitter cables. One (1) group control cable kit
is required for each indoor unit in the group except for the last
indoor unit.
Always use an LG provided group control communications
cable (Group Control Kit; sold separately) between the indoor
unit and the wall-mounted zone controller.
NEVER splice or cut the communications cable. Do not short-
en the cable or extend cable length with field provided cable.
Before running cable, decide which indoor unit will be the mas-
ter indoor unit. The zone controller connects to the master.
Adjust the appropriate DIP switch at each indoor unit in the
group to identify it as the master or a slave. On wall mounted
indoor unit models, set the assignment using the handheld
remote controller.
Use a daisy chain configuration and connect all of the group’s
indoor units together starting at the Master unit.
Communication Cable
ELECTRICAL SYSTEM INSTALLATION
CN-REMO
On All Indoor Unit Styles
CN-REMO
On All Indoor Unit Styles
CN-REMO
On All Indoor Unit Styles
LG
Supplied
LG Supplied Group Control Kit (PZCWRCG3)
CN-REMO
On All Indoor Unit Styles
LG Supplied
Cable Assembly
To CN_REMO
Connector on
IDU Control PCB
YellowBlackRed
Front Back
Figure 76:Indoor Unit to Zone
Controller Connection.
Note:
Cable connected to Zone Controller is the factory default connection.
Note:
Cable connected to Zone Controller is the factory default connection.
Figure 77:Indoor Unit Group to Zone Controller Connections.