MULTI V Water IV System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ELECTRICAL CONNECTIONS
ARWB Series Heat Recovery Systems (208-230V and 460V)
Master WSU
Indoor Units
Main Switch Slave 1 WSU Slave 2 WSU
Pull Box
(Installer option)
R
(L1)
L1
L2
Switch
Fuse
Switch
Fuse
Switch
Fuse
S
(L2)
T
(L3)
R
(L1)
S
(L2)
T
(L3)
R
(L1)
S
(L2)
T
(L3)
Power Supply
3 Phase, 60Hz
208/230V
or 460V
Power Supply
1 Phase, 60Hz
208/230V
Heat
Recovery
Unit
Pull Box
(Installer
option)
Pull Box
(Installer
option)
Pull Box
(Installer
option)
Power Cable:
Communication Cable:
CEN B CEN A
AC Smart or other Central Controller
Communications Between WSUs
Master WSU
CEN B SODU B
Slave 1 WSU
CEN A IDU AIDU BSODU A
CEN B SODU B CEN A IDU AIDU BSODU A
CEN B SODU B
Slave 2 WSU
CEN A IDU AIDU BSODU A
3 4 3 4 3 4
Communications Between IDUs and Master WSU
Master WSU
Indoor Units
CEN B SODU B CEN A IDU AIDU BSODU A
Master WSU
Indoor Units
Main Switch Slave 1 WSU Slave 2 WSU
Pull Box
(Installer option)
R
(L1)
L1
L2
Switch
Fuse
Switch
Fuse
Switch
Fuse
S
(L2)
T
(L3)
R
(L1)
S
(L2)
T
(L3)
R
(L1)
S
(L2)
T
(L3)
Power Supply
3 Phase, 60Hz
208/230V
or 460V
Power Supply
1 Phase, 60Hz
208/230V
Heat
Recovery
Unit
Pull Box
(Installer
option)
Pull Box
(Installer
option)
Pull Box
(Installer
option)
Power Cable:
Communication Cable:
CEN B CEN A
AC Smart or other Central Controller
Communications Between WSUs
Master WSU
CEN B SODU B
Slave 1 WSU
CEN A IDU AIDU BSODU A
CEN B SODU B CEN A IDU AIDU BSODU A
CEN B SODU B
Slave 2 WSU
CEN A IDU AIDU BSODU A
3 4 3 4 3 4
Communications Between IDUs and Master WSU
Master WSU
Indoor Units
CEN B SODU B CEN A IDU AIDU BSODU A
The GND terminal at the main
circuit board is a negative
terminal for a dry contact
connection. Do not connect
ground wires to this terminal.
Ensure that the terminal
connections of the master
and slave water source unit
connections are matched,
A terminals to A terminals and
B terminals to B terminals.
Note:
Never apply line voltage power to the communications cable
terminal block. If contact is made, the system may be damaged.
Always include some allowance in the wiring length when
terminating. Provide some slack to facilitate removing the electrical
panels while servicing.
Always ground indoor units to help prevent electrical shock
accidents or communication signal disruption. Do not connect
ground wires to the refrigerant pipes.
Install a main shutoff switch that interrupts all power sources
simultaneously.
Operating the system in reversed phase can damage the
compressor or other components. If there is a possibility of
reversed phase, phase loss, momentary blackout, or the power
goes on and off during operation, install a field-supplied phase loss
protection circuit.