EasyManua.ls Logo

LG Multi V Water IV - Electrical Data: ARWB Series Heat Recovery Water Source Units; 208-230 V, 60 Hz, 3-Phase Heat Recovery Electrical Data; 460 V, 60 Hz, 3-Phase Heat Recovery Electrical Data

LG Multi V Water IV
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ARWB Series Heat Recovery Water Source Units
ELECTRICAL DATA
Table 17: 208-230V, 60Hz, 3-Phase Heat Recovery Systems.
Table 18: 460V, 60Hz, 3-Phase Heat Recovery Systems.
Nom.
Tons
HP
System Model
No.
Compressor (Comp.) MCA MOCP
Comp.
Qty.
Motor RLA (Ea.)
Frame 1 Frame 2 Frame 3 Frame 1 Frame 2 Frame 3
Frame 1 Frame 2 Frame 3
6.0 8 ARWB072BAS4 1 28.0 35.0 60
8.0 10 ARWB096BAS4 1 28.4 35.5 60
10.0 12 ARWB121BAS4 1 28.8 36.0 60
12.0 14 ARWB144BAS4 1 28.8 36.0 60
14.0 18 ARWB168BAS4 2 28.4 28.0 35.5 35.0 60 60
16.0 20 ARWB192BAS4 2 28.8 28.0 36.0 35.0 60 60
18.0 22 ARWB216BAS4 2 28.8 28.0 36.0 36.0 60 60
24.0 28 ARWB288BAS4 2 28.8 28.8 36.0 36.0 60 60
30.0 36 ARWB360BAS4 3 28.8 28.8 28.0 36.0 36.0 35.0 60 60 60
36.0 42 ARWB432BAS4 3 28.8 28.8 28.8 36.0 36.0 36.0 60 60 60
For component model nos. see the specification tables on p. 14-16.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOCP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
For component model nos. see the specification tables on p. 14-16.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOCP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
Nom.
Tons
System
Model No.
Compressor (Comp.) MCA MOCP RFA
Comp.
Qty.
Motor RLA (Ea.)
Frame 1 Frame 2 Frame 3 Frame 1 Frame 2 Frame 3 Frame 1 Frame 2 Frame 3
Frame 1 Frame 2 Frame 3
6.0 ARWB072DAS4 1 13.0 16.2 25 25
8.0 ARWB096DAS4 1 13.8 17.2 25 25
10.0 ARWB121DAS4 1 15.4 19.3 25 25
12.0 ARWB144DAS4 1 20.6 25.7 45 35
14.0 ARWB168DAS4 1 21.6 27.0 45 35
16.0 ARWB192DAS4 1 22.4 28.0 50 35
20.0 ARWB240DAS4 2 20.6 13.8 25.7 17.2 45 25 35 25
24.0 ARWB288DAS4 2 21.6 15.4 27.0 19.3 45 25 35 25
28.0 ARWB336DAS4 2 21.6 21.6 27.0 27.0 45 45 35 35
32.0 ARWB384DAS4 2 22.4 22.4 28.0 28.0 50 50 35 35
40.0 ARWB480DAS4 3 22.4 20.6 20.6 28.0 25.7 25.7 50 45 45 35 35 35
48.0 ARWB576DAS4 3 22.4 22.4 22.4 28.0 28.0 28.0 50 50 50 35 35 35

Table of Contents