12
MULTI V Water IV System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
1
Nominal capacity is outside of AHRI Standard 1230 and based on the following conditions:
• Cooling – Indoor 80°F DB / 66°F WB
Water Temperature Entering: 86°F
• Heating – Indoor 68°F DB
Water Temperature Entering: 68°F
2
When entering water temperature is lower than 59ºF, variable water flow control kit PWFCKN000
is required.
3
Sound pressure levels are tested in an anechoic chamber under ISO 3745 standard.
4
Value is calculated as follows: Δt = Total Heat of Rejection/(Nominal Flow Rate x 500).
5
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configura-
tion using LG’s computerized refrigerant piping software (LATS Multi V) to validate the pipe design.
Table 4: Single-Frame 460V Heat Pump Units.
GENERAL DATA
ARWN Series Heat Pump Water Source Unit Specications
Combination Unit Model Number
6.0 Ton
ARWN072DAS4
8.0 Ton
ARWN096DAS4
10.0 Ton
ARWN121DAS4
12.0 Ton
ARWN144DAS4
14.0 Ton
ARWN168DAS4
16.0 Ton
ARWN192DAS4
Individual Component Model Numbers
– – – – – –
Cooling Performance
Nominal Cooling Capacity (Btu/h)
1
72,000 96,000 120,000 144,000 168,000 192,000
Heating Performance
Nominal Heating Capacity (Btu/h)
1
81,000 108,000 135,000 162,000 189,000 216,000
Operating Range (Entering Water Temperature)
Cooling (°F)
2
23 – 113 23 – 113 23 – 113 23 – 113 23 – 113 23 – 113
Heating (°F)
14 – 113 14 – 113 14 – 113 14 – 113 14 – 113 14 – 113
Compressor
Inverter Quantity
HSS DC Scroll x 1 HSS DC Scroll x 1 HSS DC Scroll x 1 HSS DC Scroll x 1 HSS DC Scroll x 1 HSS DC Scroll x 1
Oil/Type
PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Unit Data
Refrigerant Type
R410A R410A R410A R410A R410A R410A
R410A Refrigerant Factory Charge (lbs)
12.8 12.8 12.8 6.6 6.6 6.6
Refrigerant Control/Location
EEV/Indoor Unit EEV/Indoor Unit EEV/Indoor Unit EEV/Indoor Unit EEV/Indoor Unit EEV/Indoor Unit
Max. Number Indoor Units/System
13 16 20 23 29 32
Sound Pressure dB(A)
Cooling/Heating
47/51 50/53 56/56 58/57 53/57 54/60
Net Unit Weight (lbs.)
280 280 280 309 309 309
Shipping Weight (lbs.)
302 302 302 331 331 331
Communication Cables
2 x 18 AWG 2 x 18 AWG 2 x 18 AWG 2 x 18 AWG 2 x 18 AWG 2 x 18 AWG
Heat Rejected to Equipment Room (Btu/h)
2,152 2,322 2,493 2,357 2,459 2,561
Heat Exchanger (Stainless Steel Plate)
Maximum Pressure Resistance (psi)
640 640 640 640 640 640
Flow at Rated Condition (GPM)
20.3 25.4 30.4 35.5 45.7 50.7
Range of Flow (GPM)
8.1 – 30.5 10.2 – 38.1 12.2 – 45.6 14.2 – 53.3 18.3 – 68.6 20.3 – 76.1
Total Heat of Rejection (Btu/h)
94,100 125,900 157.900 190,100 221,100 253,500
Total Heat of Absorption (Btu/h)
74,200 98,600 122,700 146,800 170,100 193,600
Pressure Drop (ft-wg)
3.7 4.7 6.9 4.7 8.0 9.2
Δt
4
(°F)
9.3 9.9 10.3 10.7 9.7 10.0
Piping
5
Liquid Line Connection (in., OD)
3/8 Braze 3/8 Braze 1/2 Braze 1/2 Braze 1/2 Braze 1/2 Braze
Vapor Line Connection (in., OD)
7/8 Braze 7/8 Braze 1-1/8 Braze 1-1/8 Braze 1-1/8 Braze 1-1/8 Braze
Water Inlet/Outlet Connection (in)
1-1/2 + 1-1/2 Fem 1-1/2 + 1-1/2 Fem 1-1/2 + 1-1/2 Fem 1-1/2 + 1-1/2 Fem 1-1/2 + 1-1/2 Fem 1-1/2 + 1-1/2 Fem
Condensate Drain (in)
3/4 Female 3/4 Female 3/4 Female 3/4 Female 3/4 Female 3/4 Female