ERROR CODE TABLES
For detailed information on how to troubleshoot each error, see the Water Source Unit Service Manual on www.lghvac.com.
Error Code Description Possible Cause
2 0 1 C1–C16
1
HRU liquid pipe temperature sensor error
Sensor open/short
Defective temperature sensor connection
Defective temperature sensor
Defective WSU PCB
2 0 2 C1–C16
1
HRU sub-cooling inlet pipe temperature sensor
error
Sensor open/short
Defective temperature sensor connection
Defective temperature sensor
Defective WSU PCB
2 0 3 C1–C16
1
HRU sub-cooling discharge pipe temperature
sensor error
Sensor open/short
Defective temperature sensor connection
Defective temperature sensor
Defective WSU PCB
2 0 4 C1–C16
1
Communication error Communication between WSU and HRU has failed
Table 77: Heat Recovery Unit Error Codes.