Table 11: Dual-Frame 460V Heat Recovery Units.
GENERAL DATA
ARWB Series Heat Recovery Water Source Unit Specications
Combination Unit Model Number
20.0
ARWB240DAS4
24.0
ARWB288DAS4
28.0 Ton
ARWB336DAS4
32.0
ARWB384DAS4
Individual Component Model Numbers
ARWB096DAS4 x 1
+ARWB144DAS4 x 1
ARWB121DAS4 x 1
+ARWB168DAS4 x 1
ARWB168DAS4 x 2 ARWB192DAS4 x 2
Cooling Performance
Nominal Cooling Capacity (Btu/h)
1
240,000 288,000 336,000 384,000
Heating Performance
Nominal Heating Capacity (Btu/h)
1
270,000 324,000 378,000 432,000
Operating Range (Entering Water Temperature)
Cooling (°F)
2
23 – 113 23 – 113 23 – 113 23 – 113
Heating (°F)
14 – 113 14 – 113 14 – 113 14 – 113
Synchronous Operation (°F)
23 – 113 23 – 113 23 – 113 23 – 113
Compressor
Inverter Quantity
HSS DC Scroll x 2 HSS DC Scroll x 2 HSS DC Scroll x 2 HSS DC Scroll x 2
Oil/Type
PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Unit Data
Refrigerant Type
R410A R410A R410A R410A
R410A Refrigerant Factory Charge (lbs)
12.8 + 6.6 12.8 + 6.6 6.6 + 6.6 6.6 + 6.6
Refrigerant Control/Location
EEV/Indoor Unit EEV/Indoor Unit EEV/Indoor Unit EEV/Indoor Unit
Max. Number Indoor Units/System
2
39 45 55 61
Sound Pressure dB(A)
3
Cooling/Heating
57/57 59/58 59/61 56/61
Net Unit Weight (lbs.)
280 + 309 280 + 309 309 + 309 309 + 309
Shipping Weight (lbs.)
302 + 331 302 + 331 331 + 331 331 + 331
Communication Cables
2 x 18 AWG 2 x 18 AWG 2 x 18 AWG 2 x 18 AWG
Heat Rejected to Equipment Room (Btu/h)
4,679 4952 4918 5122
Heat Exchanger (Stainless Steel Plate)
Maximum Pressure Resistance (psi)
640 640 640 640
Flow at Rated Condition (GPM)
25.4 + 35.5 30.4 + 45.7 45.7 + 45.7 50.7 + 50.7
Range of Flow (GPM)
24.4 – 91.4 30.4 – 114.2 36.6 – 171.4 40.6 – 152.1
Total Heat of Rejection (Btu/h)
125,900 + 190,100 157,900 + 221,100 221,100 x 2 253,500 x 2
Total Heat of Absorption (Btu/h)
98,600 + 146,800 122,700 + 170,100 170,100 x 2 193,600 x 2
Pressure Drop (ft-wg)
4.7 + 4.7 6.9 + 8.0 8.0 + 8.0 9.2 + 9.2
Δt
4
(°F)
10.4 10.0 9.7 10.0
Piping
5
Liquid Line Connection (in., OD)
3/8 + 1/2 Braze 1/2 + 1/2 Braze 1/2 + 1/2 Braze 1/2 + 1/2 Braze
Low Pressure Vapor Line Conn (in., OD)
7/8 + 1-1/8 Braze 7/8 + 1-1/8 Braze 1-1/8 + 1-1/8 Braze 1-1/8 + 1-1/8 Braze
High Pressure Vapor Line Conn (in., OD)
3/4 + 3/4 Braze 3/4 + 3/4 Braze 3/4 + 3/4 Braze 3/4 + 3/4 Braze
Water Inlet/Outlet Connection Size (in)
(1-1/2 + 1-1/2 Fem) x2 (1-1/2 + 1-1/2 Fem) x2 (1-1/2 + 1-1/2 Fem) x2 (1-1/2 + 1-1/2 Fem) x2
Condensate Drain (in)
3/4 Female 3/4 Female 3/4 Female 3/4 Female
1
Nominal capacity is outside of AHRI Standard 1230 and based on the following conditions:
Cooling – Indoor 80°F DB / 66°F WB
Water Temperature Entering: 86°F
Heating – Indoor 68°F DB
Water Temperature Entering: 68°F
2
When entering water temperature is lower than 59ºF, variable water flow control kit PWFCKN000
is required.
3
Sound pressure levels are tested in an anechoic chamber under ISO 3745 standard.
4
Value is calculated as follows: Δt = Total Heat of Rejection/(Nominal Flow Rate x 500).
5
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configura-
tion using LG’s computerized refrigerant piping software (LATS Multi V) to validate the pipe design.