MULTI V Water IV System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Y-Branch Kits
LG Y-branch and kits are highly engineered devices designed to evenly divide the flow of re-
frigerant, and are used to join one pipe segment to two or more segments. There are two types
of Y-branches used in LG VRF systems: Y-branches that combine two or three water source
units to make one large-capacity water source unit (also known as multi-frame connectors), or
Y-branches used with the indoor units in the refrigerant piping system at each transition. Field-
supplied “T” fittings or “Y” branches will not be accepted. Do not install Y-branches backwards;
refrigerant flow cannot make U-turns through Y-branches. The equivalent pipe length of each
Y-branch (1.6′) must be added to each pipe segment entered into LATS piping design software.
REFRIGERANT PIPING INSTALLATION
LG Engineered Y-branch Kits and Header Kits
Figure 22: Y-Branch Horizontal Conguration End View.
±5°
Horizontal Plane
±5°
Branch Leg
Straight-through Leg
Y-branch Inlet
To next branch
To indoor unit
Figure 23: Incorrect WSU
Y-branch Installation.
No Substitutions
Only LG supplied Y-branch ttings can be used to join one pipe segment to two or more segments. Third-party or eld-fabricated Tee’s, Y-ttings,
Headers, or other branch ttings are not qualied for use with LG Multi V IV systems. The only eld-provided ttings allowed in a Multi V IV piping
system are 45° and 90° elbows.
Y-Branch Kits Header Kits
Heat Pump (HP) Heat Recovery (HR)
4 Branch 7 Branch 10 Branch
WSU IDU WSU IDU
ARCNN21 ARBLN01621 ARCNB21 ARBLB01621 ARBL054 ARBL057 ARBL1010
ARCNN31 ARBLN03321 ARCNB31 ARBLB03321 ARBL104 ARBL107 ARBL2010
ARBLN07121 ARBLB07121
ARBLN14521 ARBLB14521
Table 44:Y-Branch and Header Kits.
If the diameter of the branch pipe segments differ from that of the designated refrigerant piping, trim the to the desired section using a pipe
cutter, and then use an adapter to connect.
Always follow manufacturer’s guidelines on refrigerant piping restrictions such as maximum length, elevation difference, and diameters.
Failure to do so can result in reduced heating / cooling performance or equipment malfunction.
To indoor unit
To indoor unit
To Water Source Unit
Figure 20: Top View of Indoor Unit Y-branch
Horizontal Installation.
Figure 21: Indoor Unit Y-branch Vertical
Installation Alignment Specication.
Vertical up
conguration
Vertical down
conguration
LG Y-Branch Kits Consist of:
Y-branches:
- For heat pump systems - one liquid line and one vapor line (two [2] total)
- For heat recovery systems - one liquid line, one low-pressure vapor line, and
one high-pressure vapor line (three [3] total)
Reducer fittings as applicable.
Molded clam-shell type peel and stick insulation covers.
Indoor Unit Y-Branches
Indoor unit Y-branches may be installed in hori-
zontal or vertical configurations. When installed
vertically, position the Y-branch so the straight-
through leg is within ±3° of plumb. When installed
horizontally, position the Y-branch so the take-off
leg is level and shares the same horizontal plane
as the straight-through leg within ±5° rotation.
Indoor unit Y-branches must always be installed
with the single port end towards the water source
unit, the two-port end towards the indoor units
(or heat recovery units for heat recovery sys-
tems only). If indoor unit Y-branches are used to
combine heat recovery ports to accommodate an
indoor unit with a capacity of six (6) tons or larger,
then the single port end must be installed with the
single port end towards the indoor unit and the two-