EasyManua.ls Logo

LG Multi V Water IV - Page 56

LG Multi V Water IV
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56
MULTI V Water IV System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Anticipated Linear
Expansion (LE) (in)
Nominal Tube Size (OD) inches
1/4 3/8 1/2 3/4 1 1-1/4 1-1/2
1/2
R
1
6 7 8 9 11 12 13
L
2
38 44 50 59 67 74 80
1
R
1
9 10 11 13 15 17 18
L
2
54 63 70 83 94 104 113
1-1/2
R
1
11 12 14 16 18 20 22
L
2
66 77 86 101 115 127 138
2
R
1
12 14 16 19 21 23 25
L
2
77 89 99 117 133 147 160
2-1/2
R
1
14 16 18 21 24 26 29
L
2
86 99 111 131 149 165 179
3
R
1
15 17 19 23 26 29 31
L
2
94 109 122 143 163 180 196
3-1/2
R
1
16 19 21 25 28 31 34
L
2
102 117 131 155 176 195 212
4
R
1
17 20 22 26 30 33 36
L
2
109 126 140 166 188 208 226
1
R = Center line Length of Pipe.
2
L = Center line Minimum Radius (inches).
Large Tubing U-bend (>3/4 in.) Loop Small Tubing U-bend (<3/4 in.)
Figure 28: Coiled Expansion Loops and Offsets.
R
L
L
R
L
Table 46: Radii of Coiled Expansion Loops and Developed Lengths of Expansion Offsets.
R
L
L
R
L
R
L
L
R
L
REFRIGERANT PIPING INSTALLATION

Table of Contents

Related product manuals