Water Circuit Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Water Quality Requirements
Impurities in the water can influence the performance and life expectancy of the water cooled unit. Use a local water treatment professional
to test and treat the water. Maintain the following levels:
Basic Item
Closed Type System Effect
Circulating Water Supplemented Water Corrosion
1
Scale
1
pH (77°F) 7.0 ~ 8.0 7.0 ~ 8.0
Conductivity (77°F) mS/m Below 30 Below 30
Chlorine ions (mg Cl
-
/ℓ) Below 50 Below 50
Sulfate ions (mg SO
4
2
/ℓ) Below 50 Below 50
Acid consumption (pH4.8) (mgCaCO
3
/ℓ) Below 50 Below 50
Total Hardness (mg CaCO
3
/ℓ) Below 70 Below 70
Calcium Hardness (mg CaCO
3
/ℓ) Below 50 Below 50
Ionic-static silica (mg SiO
2
/ℓ) Below 30 Below 30
Reference Item
Iron (mg Fe/ℓ) Below 1.0 Below 0.3
Copper (mg Cu/ℓ) Below 1.0 Below 0.1
Sulfate ion (mg SO42/ℓ) Must not be detected Must not be detected
Ammonium ion (mg NH4+)ℓ Below 0.3 Below 0.1
Residual chlorine (mg Cl/ℓ) Below 0.25 Below 0.3
Free carbon dioxide (mg CO
2
/ℓ) Below 0.4 Below 4.0
Stability index
1
The “●” mark for corrosion and scale means that there is a possibility of occurrence.
Use inhibitors in the water loop, especially if water temperature operates above 104°F.
Purge air from the system.
Note:
WATER CIRCUIT INSTALLATION
Piping System Specications
Pipe Insulation
Water pipe insulation is suggested in the following conditions:
If water pipe is subject to freezing.
If water can condense on surface of pipe from ambient room temperatures higher than temperature of water in the pipe.
On boiler water pipes to save energy losses from heat source.
On condensate drain lines.
Where required by local code.
If water temperature is maintained at 68°F in winter and 86°F in summer, insulation is not required (unless required by local code).
Table 61:Minimum Water Quality Requirements.