Pre-commissioning and Maintenance
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Central Control
PRE-COMMISSIONING
Central Control Device Maximum Indoor Unit Quantity
AC EZ 32
AC SMART Premium 128
LonWorks Gateway 64
BACnet Gateway 256
Advanced Control Platform 256
Table 68:Central Controller Indoor Unit Connection Limitations.Each type of central controller device has a maximum number of
indoor units it can communicate with.
The quantity of indoor units that can be connected to a single
central control communications cable, therefore, will be defined by
the central control device on that cable with the smallest Maximum
Indoor Unit Quantity as shown at right.
Central Controller Communications Limitations
Group Number
If the building operator wants to know which indoor units are on each
water source unit, and multiple systems serve a building, assign a
Group Number to each system. If there are more than 16 indoor units on a system, multiple Group Numbers may be necessary.
If the building owner wants to know which indoor units are on each floor, assign a different group number for each floor. If there are more
than 16 indoor units on a floor, multiple Group Numbers may be necessary.
Member Number
Can be assigned as desired or for example, can follow the room layout on each floor.
For each LG Central Controller product provided on the project, devise a central control address schedule and assign a central control ad-
dress to each indoor unit(s) Hydro Kit(s), and ERV(s) units. Record this central control address for each component in the column provided
on the Pre-commissioning Device Configuration Worksheet.
Upload Central Control Address to the Indoor Units
For all ducted, vertical and floor standing indoor units, the central control address must be assigned using a wired zone controller. Wall-
mount, ceiling cassette, ceiling suspended, and the wall/ceiling convertible indoor units, the central control address can be assigned using a
wireless handheld controller or a wired zone controller.
Power Up All Indoor Unit PCBs
Turn the disconnect for each indoor unit to the “ON” position. DO NOT turn the unit ON (on/off button remains off).